(working days). A copy of the letter must be On delivery we recommend that you keep the key which is addressed to Lennox and the supplier or distributor for attached to an eyebolt in a safe and accesible place. This information purposes.
Page 7
TRANSPORT - HANDLING FC.../FH.../FD.../FG... 060 & 070 with centrifugal fans Sling length = 2590 mm Sling length = 1855 mm for angle = 45°C for angle = 45°C FC.../FH.../FD.../FG... 085 & 100 Sling length = 2830 mm for angle = 45°C Sling length = 2330 mm for angle = 64,5°C FC.../FH.../FD.../FG...
Page 8
TRANSPORT - HANDLING FC.../FH.../FD... 120 & 140 Sling length = 2080 mm Sling length = 2700 mm for angle = 45°C for angle = 45°C FC.../FH.../FD... 120 & 140 with centrifugal fans Sling length = 2410 mm for angle = 45°C Sling length = 3000 mm for angle = 45°C Sling length = 1880 mm...
Page 9
TRANSPORT - HANDLING FG... 120 & 140 with gas burner and centrifugal fans Sling length = 3300 mm Sling length = 2700 mm for angle = 45°C for angle = 45°C Sling length = 2080 mm for angle = 45°C FC.../FH.../FD...
Page 10
TRANSPORT - HANDLING FX 25 & 30 Sling length = 3000 mm FX 35 - 40 - 55 Sling length = 3700 mm FX 70 - 85 - 100 Sling length = 3900 mm FX 110 - 140 - 170 Sling length = 4300 mm IOM / ROOF-TOP FLEXY™...
INST T T T T ALLA ALLA ALLA ALLA ALLATION TION TION TION TION PRELIMINARY CHECK INSTALLATION DEVICE Before installing the equipment, the following items MUST be The surface on which the equipment is to be installed must checked : be clean and free of any obstacles which could hinder the flow of air to the condensers: - Is there sufficient space for the equipment?
INSTALLATION ON A ROOFMOUNTING FRAME levels are adjustable, observe the following recommendations for correct installation of the equipment. Above all, ensure that all the flaps are facing outward (1 - figure 5). They are sometimes stored inside for transport. Figure 5 Place the roof mounting frame on the trimmer beam by first lining up the inlet and then the outlet.
Page 13
INSTALLATION ON A ROOFMOUNTING FRAME When the frame is correctly positioned, it is essential to secure the assembly with a disconnected welding seam (20 to 30 mm for every 200 mm) along the outside, or by using an alternative method (1 - figure 8). Figure 8 Assembly joint (1 - figure 9) Insulate the frame before installation.
INSTALLATION ON POSTS The unit can be fitted on corner posts using the frame provided. The minimum height of the posts should be 400mm. Figure 10 IOM / ROOF-TOP FLEXY™ Series - Page 13...
COMMISSIONING This work must only be carried out by trained refrigeration engineers Before connecting to the power : Safety Test - Ensure that the power supply between the building and - "Clogged filter" detection test : vary the setpoint value the unit meets local authority standards and that the (KP02 setpoint 93) in respect to the air pressure value cable specification satisfies the start-up and operating...
AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING The actual resistance of ductwork systems is not always the same as the calculated theoretical values. To rectify this, it may be necessary to modify the pulley and belt setting. To this effect, the motors are fitted with variable pulleys.
Page 17
AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING UNIT/FAN KIT REFERENCE TABLE CHART (see following pages) Size Fan type FCx or FHx FGx or FDx FCx or FHx Centrifugal condensor 1 (*) FGx or FDx FCx or FHx Centrifugal condensor 1 (*)
Page 18
AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING EXAMPLE : You may want to adjust a FHK 120 set to 22 000 m /h with a system resistance of 150Pa: The machine has 2 fans (chart D). For this operating point, the unit supplied is fitted with E kits comprising 112 mm - 131 mm variable pulleys on the motors and 250 mm pulleys on the fans.
Page 19
AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING CHART A Page 18 - IOM / ROOF-TOP FLEXY™ Series...
Page 20
AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING CHART B IOM / ROOF-TOP FLEXY™ Series - Page 19...
Page 21
AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING CHART C Page 20 - IOM / ROOF-TOP FLEXY™ Series...
Page 22
AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING CHART D IOM / ROOF-TOP FLEXY™ Series - Page 21...
Page 23
AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING CHART E Page 22 - IOM / ROOF-TOP FLEXY™ Series...
Page 24
AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING AIR FLOW BALANCING CHART F IOM / ROOF-TOP FLEXY™ Series - Page 23...
AIRFLOW BALANCING - FXA/FXK AIRFLOW BALANCING - FXA/FXK AIRFLOW BALANCING - FXA/FXK AIRFLOW BALANCING - FXA/FXK AIRFLOW BALANCING - FXA/FXK The FX* models are designed to operate with more complex A. Set the unit to the "recycle air" position (figure 15) supply and extract ductwork systems.
filters ters ters ters ters The CLIMATIC™ controls the filters. Two types of problems may occur : 1 - 004 error code (lit LED “filter”) or the following icon (for a graphics screen - KP07) : Item 8 on KP 17 indicates that the filters must be changed. The unit has not stopped but the airflow is likely to be reduced due to increased pressure drop acros the filters.
HOT W T WA A A A A TER COILS TER COILS TER COILS TER COILS TER COILS HYDRAULIC CONNECTIONS ELECTROLYTIC CORROSION The heating coil is connected to the isolating valves. Two keys Attention is drawn to the corrosion problems resulting from must be used to tighten the connections, one of the keys electrolytic reaction created from unbalanced earth maintains the valve body.
GAS BURNER GAS BURNER GAS BURNER GAS BURNER GAS BURNER PRELIMINARY CHECKS ON IGNITION DETAILS COMMISSIONING Make sure that the gas line valves are open. NOTE : Any work on the gas system must only be carried With the ROOF TOP working (Setpoint 06 to ON), adjust out by qualified personnel.
Page 29
GAS BURNER GAS BURNER GAS BURNER GAS BURNER GAS BURNER PRESSURE REDUCING VALVE SETTING - Connect the tube of the manometer to the power pressure inlet of a solenoid valve (5-figure 24) after loosening the screw. - Remove the safety plug of the expansion valve setting. - Use a screwdriver to pre-set by placing the screw at a depth of 34 mm.
Page 30
GAS BURNER GAS BURNER GAS BURNER GAS BURNER GAS BURNER IGNITION ELECTRODE The following two checks can be made : - Ensure that the electrode tip (1 – figure 25) is always sharp and oxide-free. Use some sand paper to clean it, if necessary.
Page 31
GAS BURNERS GAS BURNERS GAS BURNERS GAS BURNERS GAS BURNERS BURNER DISASSEMBLY FOR SERVICE TROUBLESHOOTING AND MAINTENANCE PURPOSES The fan does not work. - Check the electrical supply as well as the CLIMATIC™ Please refer to the enlarged diagrams at the end of the section which should show a heat demand.
Page 32
GAS BURNERS GAS BURNERS GAS BURNERS GAS BURNERS GAS BURNERS 60 KW BURNER FOR FGX 60 AND 70 MODELS Figure 30 IOM / ROOF-TOP FLEXY™ Series - Page 31...
Page 33
GAS BURNER GAS BURNER GAS BURNER GAS BURNER GAS BURNER 120 KW BURNER FOR FGX 60, 70 AND 100 MODELS Figure 31 Page 32 - IOM / ROOF-TOP FLEXY™ Series...
Page 34
GAS BURNER GAS BURNER GAS BURNER GAS BURNER GAS BURNER 180 KW BURNER FOR FGX 120 AND 140 MODELS Figure 32 IOM / ROOF-TOP FLEXY™ Series - Page 33...
BELT TENSION T TENSION T TENSION T TENSION T TENSION On delivery, the drive belts are new and correctly tensioned. After the first 50 operating hours check and adjust the tension. 80% of the total elongation of belts is generally produced during the first 15 hours of operation.
PULLEYS PULLEYS PULLEYS PULLEYS PULLEYS FAN PULLEY REMOVAL Remove the 2 screws and put one of them in the extraction threaded screw. Screw in fully. The hub and the pulley will separate from each other. Remove the hub and the pulley by hand without damaging the machine. Figure 35 FAN PULLEY INSTALLATION Clean and de-grease the shaft, hub and conical bore of the pulley.
USING THE KP 17 COMFORT CONTROL DISPLAY The CLIMATIC™ 'Comfort' control Display allows an untrained person to easily operate a Lennox Roof-Top. This display connects to a single Rooftop and, through the use of the control keys, LED's and display the user can see...
USING THE KP02 MAINTENANCE CONTROL DISPLAY This display unit allows you to read and modify all the values The dialogue with the controller is initiated by the CLIMATIC™. of the variables or setpoints of the rooftop to which it is If, after 3 attempts, no communication is established, a connected.
Page 39
USING THE KP02 MAINTENANCE CONTROL DISPLAY Variable or setpoint value Digital Values 1 <--> ON 0 <--> OFF Temperatures Temperatures are displayed in °C, to an accuracy of 0.1 °C <--> -21.6 °C <--> + 105.8 °C Pressures Pressure is given in bars, to an accuracy of 0.1 bar. <-->...
Page 40
USING THE KP02 MAINTENANCE CONTROL DISPLAY If the password code is correct, the following message will 2 - OPERATING MODES appear when key [V] is released : The maintenance display allows for 4 modes of operation. Key [M] allows you to move successively and in a loop from one mode to the next.
Page 41
USING THE KP02 MAINTENANCE CONTROL DISPLAY For different types of data, the setting ranges are as follows : Item Minimum value Maximum value Hours and minutes 00-00H 23-59 H Day of the month Day of the week Month Year Changes are only incorporated when key [A] is pressed. NOTE : The compatibility of the value for the day of the month is not checked when it is entered.
Page 42
USING THE KP02 MAINTENANCE CONTROL DISPLAY LIST OF SETPOINTS 1st Level Min. Factory Maxi. Password to access level 2 setpoints and variables Temperature, required setpoint for room, day mode 21.0 35.0 (Used by KP17 only) KP17 Remote control, overide, occupied mode (Used by KP17 only) KP17 Remote control, overide, automatic mode (Used by KP17 only)
Page 43
USING THE KP02 MAINTENANCE CONTROL DISPLAY Min. Factory Maxi. (FLEXY™ only) Mode, Fan low speed, dead zone (FLEXY™ only) Mode, Fan low speed automation (on = unit runs at maximum 50% during "night mode") Mode, Low noise (J-BUS only) Remote control, overide, Mode (J-BUS only) Remote control, Overide, Low fan speed (J-BUS only)
Page 44
(on LINEA™ only)* - (R22 = -3, R407C = 1) -10.0 -3.0 Battery temperature, setpoint, authorised defrosting, condenser coil * : LINEA is another range of LENNOX ROOFTOP. For more information, please consult your regional office IOM / ROOF-TOP FLEXY™ Series - Page 43...
Page 45
EPROM values (centre column) Test stages (for factory test procedures only reduces all delay timers to 0) 65535 * : LINEA is another range of LENNOX ROOFTOP. For more information, please consult your regional office Page 44 - IOM / ROOF-TOP FLEXY™ Series...
Page 46
USING THE KP02 MAINTENANCE CONTROL DISPLAY VARIABLE LIST (june 2001) 1st Level Error code Temperature, room Relative humidity (%),room Temperature, outside air Relative humidity (%), outside, air Temperature, supply Air Temperature, chilled water battery Temperature, compressor, no. 1 Temperature, compressor, no. 2 Temperature, compressor, no.
Page 47
USING THE KP02 MAINTENANCE CONTROL DISPLAY Output, low speed supply fan Output, Extract fan Output, compressor, no. 1 Output, compressor, no. 2 Output, compressor, no. 3 Output, compressor, no. 4 Output, compressor, no. 1, hot gas injection valve Output, compressor, no. 1, cycle reversing valve Output, compressor, no.
- Recording of successive status of pre-defined variables to create analog and event histories. A KP07 unit can be attached to more than 8 LENNOX Rooftops, providing they have the same software. The function of these keys may vary from one screen to The link between the controllers and the display is serial and another and is defined on the active screen by an icon.
Page 49
Through "MODIFICATION" mode, the user is able to : - choose the number of the controller he wishes to see Pressing on this key activates the "modification" mode the variables of (if several LENNOX Rooftops are (see below). attached to the same KP07 display unit), - control the setpoints.
Page 50
USING THE KP07 GRAPHIC CONTROL DISPLAY GENERAL SCREEN LAYOUT Summary Measurements : Chart : Temperatures Ambient temperature Measurements : Chart : Humidity Ambient humidity Operational status : History : Ventilation Safety & Errors Hourmeters : Ventilation, customer... Operational status : History : Frost Safety &...
Page 51
USING THE KP07 GRAPHIC CONTROL DISPLAY Password : Level 1 Settings : On/Off Settings : Settings : On ; Ventilation Condition ; Day Settings : Settings : Condition ; Weekend On ; Ventilation Settings : Time Settings : Settings : On ;...
Page 52
USING THE KP07 GRAPHIC CONTROL DISPLAY Settings : Settings : Condition ; BMS On ; Ventilation Settings : Control ; Cold Settings : Control ; Hot Settings : Control. ; Dehumidification Settings : Control ; Humidification Settings : Control ; Misc. Settings : Limits ;...
Page 53
USING THE KP07 GRAPHIC CONTROL DISPLAY INDEX OF ICONS Keys Select variable to change Select digit to change. Increase value Enter current change. Go to temperature and humidity values and charts. Go to the machine component status. Go to various notices. Go to room temperature chart.
Page 54
USING THE KP07 GRAPHIC CONTROL DISPLAY Sensors Temperature sensor Humidity sensor Pressure sensor Return or room data Supply data Outside data Operating conditions Operating condition: Day Operating condition: Weekend Operating condition: Night Operating condition: Morning Operating condition: Noon Operating condition: Evening Operating condition: BMS Operating status Cooling mode setting operation.
Page 55
USING THE KP07 GRAPHIC CONTROL DISPLAY Compressor defrosting. Compressor stopped in anti-short cycle. (On / Off) Condenser (On / Off) Gas grade. Half flow gas. (On / Off) Hot proportional valve, hot water valve. (On / Off) Electrical heaters. (On / Off) Humidifier (On / Off) Dehumidification (On / Off) Pump Errors...
Page 56
USING THE KP07 GRAPHIC CONTROL DISPLAY (Start / End) [091] Faulty processing fan. (Start / End) [001] Wrong air flow. (Start / End) [099] Error smoke. (Start / End) [004] Dirty filters. (Start / End) [005] Missing filters. (Start / End) [115][125][135][145] Faulty high pressure or faulty electrical compressor.
BMS VOLT FREE CONTACTS KIT This option is used for making a connection to the BMS only, by a set of hard contacts. It requires the addition of a KP05 card, if this is not already in place, and a KP12 card. Input connection must be by screened cable only.
CLIMATIC™ PARAMETERS ON - OFF The five available time slots are : The unit is declared On if setpoint 6 (C06) is ON. WEEK-END The unit can be stopped by a remote control command by hard contact. On KP12 extension card - see chapter on BMS contact kit. NIGHT For certain configurations a CLIMATIC™...
Page 59
CLIMATIC™ PARAMETERS DESCRIPTION OF PARAMETERS Parameters are defined for the time slot. Select by instruction 08 setting. 0 = DAY / 1 = WEEKEND / 2 = NIGHT / 3 = unused / 4 = MORNING / 5 =MIDDAY / 6 = EVENING / 7 = BMS. Instruction Description Day of the week of start of setting .
Page 60
CLIMATIC™ PARAMETERS ORDER OF COMPONENTS IN REGULA- ADVANCE ACTIVATION OF THE MORNING TION SLOT Cooling operation Depending on the thermal inertia of the building or the installation and external climatic conditions, it is possible to Setpoint 58 = advance the switch from the NIGHT slot to the MORNING Damper è...
Page 61
Inversion by setpoint 59 Inversion by Inversion by setpoint 58 setpoint 60 Inertia 100% zone 3-way valve or water coil Damper 3-way valve Min. fresh Heating Air conditioning setpoint 16 setpoint 15 Differential in heating Hysteresis in heating Hysteresis in air cond.
Page 62
CLIMATIC™ PARAMETERS REGULATION OF SUPPLY AIR REGULATION IN HUMIDITY Supplying air regulation should be activated by setting setpoint Two power factors, one for dehumidifying (variable 105), the 61 to ON. other for humidifying (variable 104), are calculated according to the difference in relative hygrometry between the setpoint The main aim of supplying air regulation is to maintain the and the reference relative hygrometry.
Page 63
CLIMATIC™ PARAMETERS REGULATION IN DEHUMIDIFYING 3rd stage 2nd stage 1st stage Hysteresis Activation differential Dehumidification (setpoint 69) (setpoint 70) Hysteresis Activation differential (setpoint 69) (setpoint 70) Hysteresis (setpoint 69) ENTHALPY FUNCTION REGULATION IN HUMIDIFYING This function is used to control the use of the economiser register according to air enthalpy.
ELECTRICITY ELECTRICITY ELECTRICITY ELECTRICITY ELECTRICITY The power cable should be connected to the main isolating In the following pages you will find references to electrical switch and is fed from the underside of the unit into the diagrams which will allow you to select the wiring for your electrical panel.
Page 65
-QE1 -QE2 -QF1 TRI : 400V 50Hz + T PA : ... kW -KM1 -KM2 -KE1 -KE2 -KM5 FOLIO IN : ... A 04/7 ID : ... A A1 A2 400V -MS1 -MS2 -ME1 300VA -B19 -B20 -B23 T> T> T>...
Page 73
+18V +18V 12V.H 12V.G 200mA Remote control stop Remote control night Remote control day Load limit 50% Disable heating Disable cooling Customer status Filter alarm Blower alarm Compressor alarm Gas heat alarm or electric heat alarm High temperature alarm Low temperature alarm Humidifier alarm Customer control...
Page 74
ELECTRICAL WIRING DIAGR ELECTRICAL WIRING DIAGR ELECTRICAL WIRING DIAGRAMS ELECTRICAL WIRING DIAGR ELECTRICAL WIRING DIAGR G43x60 L = 700 mm G43x60 L = 1010 mm -X1 -X2 -X3 G43x60 L = 1200 mm KP17.1 FCA/FHA 050 FCK/FHK 050 G60x80 L = 100 mm G30x80 L = 1315 mm G60x80 L = 1040 mm KP17.1...
ELECTRICAL WIRING DIAGR ELECTRICAL WIRING DIAGR ELECTRICAL WIRING DIAGR ELECTRICAL WIRING DIAGR ELECTRICAL WIRING DIAGRAMS lis AMS lis AMS lis AMS lis AMS list of itemS t of itemS t of itemS t of itemS t of itemS +A0 ..CLIMATIC™ controller -E7/8 ..
Page 76
ELECTRICAL WIRING DIAGR ELECTRICAL WIRING DIAGR ELECTRICAL WIRING DIAGRAMS lis ELECTRICAL WIRING DIAGR ELECTRICAL WIRING DIAGR AMS lis AMS lis AMS lis AMS list of itemS t of itemS t of itemS t of itemS t of itemS -Q1/2 ..Blower fan motor -MS1/-MS2 protection -SB1 ..
Page 77
SAFETY AND ERROR CODES No error Failure air flow Dirty filters Missing filters Faulty electrical heater batteries Supply air overtemperature Temperature too low Faulty gas burner no. 1 Faulty gas burner no. 2 Supply temperature too low Room overtemperature Faulty humidifier Room humidity too low Room overtemperature Faulty pump...
SAFETY AND ERROR CODES The following text includes references such as [C11] and [V25]. They relate to the threshold or variable numbers used with the KP02 unit. Wrong Air Flow If the pressure differential obtained by the analog sensor [V16] is less than the setpoint value [C92] for more than 20 seconds, and if the blower fan has operated for more than 1 minute 30 seconds, the air flow safety system is activated and stops the ventilation.
Page 79
SAFETY AND ERROR CODES register time set to 5 seconds. In addition, if the antifreeze thermostat is opened, the 3rd safety level is immediately automatically maintained. In this case, manual resetting of the thermostat followed by the CLIMATIC™ is obligatory Room Overtemperature Safety System Upper Room Air Limit If the room temperature is greater than or equal to the setpoint [C41], the safety system is...
Page 80
SAFETY AND ERROR CODES Sensor Status Room temperature sensor missing or faulty. Room relative humidity sensor missing or faulty Outside air temperature sensor faulty Outside relative humidity sensor faulty Supply Air temperature sensor faulty Temperature sensor on cold water loop faulty Temperature sensor on condenser water outlet faulty.
Page 81
SAFETY AND ERROR CODES Customer error A fault has been detected, external to the unit. Water leak If the contact of the water leak detection card is closed for more than 30 seconds, the safety system is activated. WATER HEAT EXCHANGER OUTLET TEMPERATURE SAFETY SYSTEM. Condenser Water Temperature Too Low If the temperature of the water loop is less than or equal to the preset setpoint [C89] during the operation of one of the compressors, the condenser safety mechanism is applied.
Page 82
SAFETY AND ERROR CODES Refrigeration system faults Faulty condenser temperature sensor Faulty pressure transmitter sensor, refrigeration system Faulty refrigeration system, frost temperature sensor High pressure switch safety or compressor electrical safety The compressor contactor is not connected although the CLIMATIC™ requests it. - The high pressure pressostat is open.
Before Calling for Assistence Fan stops following thermal relay cutout - The network voltage should not vary from + or - 10 % of (indicated via an error code) the supply required for the equipment, - The supply variation between the phases should never Problem : exceed + or - 3 %.
Page 84
Before Calling for Assistence The unit no longer works Cause : - No supply voltage. - Ruptured remote control fuses. - Wrong connections. Solution : - Check the supply voltage. - Check the fuses. - Check and tighten the connections. The fan rotates but the compressor does not work Problem : - The air rerun conditions are not followed.
PLANNED MAINTENANCE mixture of grease vapour and powder. For this reason we Regular maintenance of your Rooftop will extend its operating would recommend cleaning with PRESTOSOL, a de-greasing life and reduce operating faults. We recommend that the unit agent with very low toxicity, non-flammable and which does is serviced by a trained refrigeration engineer.
Page 86
PLANNED MAINTENANCE REFRIGERATION CIRCUITS At least once a year, carry out an in-depth inspection of the refrigerant circuits. In addition, before each season (or every 3 months if used permanently) the tasks listed in the maintenance contract must be performed, i.e. check the refrigerant charge, evaporation and condensing temperatures etc...
Page 87
PLANNED MAINTENANCE GENERAL MAINTENANCE SCHEDULE At least once a year after winter the equipment casing must NOTE : be cleaned, inspected and if necessary treated for corrosion. 6 monthly maintenance is performed when changing from the heating season to the air-conditioning season and vice-versa. The equipment casing is made of aluminium-zinc plate, with Annual maintenance is performed just before the start of the a polyester finish and oven-treated powder, and is ultra-violet...
Lennox shall guarantee the casing of its Rooftop units modes. manufactured since May 1991 against corrosion for 10 years commencing from the date of delivery of the material.
ISO 9001 CERTIFICA ISO 9001 CERTIFICA ISO 9001 CERTIFICA ISO 9001 CERTIFICA ISO 9001 CERTIFICATION TION TION TION TION Page 88 - IOM / ROOF-TOP FLEXY™ Series...
CE CERTIFICA CE CERTIFICA CE CERTIFICATION OF CONFORMITY CE CERTIFICA CE CERTIFICA TION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY IOM / ROOF-TOP FLEXY™ Series - Page 89...
EU4 FIL EU4 FIL EU4 FIL EU4 FIL EU4 FILTER FIRE CLASS TER FIRE CLASS TER FIRE CLASS TER FIRE CLASS TER FIRE CLASS Page 90 - IOM / ROOF-TOP FLEXY™ Series...
33 kW GAS BURNER CE CERTIFICA 33 kW GAS BURNER CE CERTIFICA 33 kW GAS BURNER CE CERTIFICATION OF CONFORMITY 33 kW GAS BURNER CE CERTIFICA 33 kW GAS BURNER CE CERTIFICA TION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY IOM / ROOF-TOP FLEXY™...
60 kW GAS BURNER CE CERTIFICA 60 kW GAS BURNER CE CERTIFICA 60 kW GAS BURNER CE CERTIFICA 60 kW GAS BURNER CE CERTIFICA 60 kW GAS BURNER CE CERTIFICATION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY Page 92 - IOM / ROOF-TOP FLEXY™...
120 kW GAS BURNER CE CERTIFICA 120 kW GAS BURNER CE CERTIFICA 120 kW GAS BURNER CE CERTIFICATION OF CONFORMITY 120 kW GAS BURNER CE CERTIFICA 120 kW GAS BURNER CE CERTIFICA TION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY IOM / ROOF-TOP FLEXY™...
180 kW GAS BURNER CE CERTIFICA 180 kW GAS BURNER CE CERTIFICA 180 kW GAS BURNER CE CERTIFICA 180 kW GAS BURNER CE CERTIFICA 180 kW GAS BURNER CE CERTIFICATION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY TION OF CONFORMITY Page 94 - IOM / ROOF-TOP FLEXY™...
INSULA INSULA INSULATION FIRE CLASS INSULA INSULA TION FIRE CLASS TION FIRE CLASS TION FIRE CLASS TION FIRE CLASS IOM / ROOF-TOP FLEXY™ Series - Page 95...
Page 97
INSULA INSULA INSULA INSULA INSULATION FIRE CLASS TION FIRE CLASS TION FIRE CLASS TION FIRE CLASS TION FIRE CLASS Page 96 - IOM / ROOF-TOP FLEXY™ Series...
Page 98
INSULA INSULA INSULATION FIRE CLASS INSULA INSULA TION FIRE CLASS TION FIRE CLASS TION FIRE CLASS TION FIRE CLASS IOM / ROOF-TOP FLEXY™ Series - Page 97...
Page 99
INSULA INSULA INSULA INSULA INSULATION FIRE CLASS TION FIRE CLASS TION FIRE CLASS TION FIRE CLASS TION FIRE CLASS Page 98 - IOM / ROOF-TOP FLEXY™ Series...
Page 100
: + 31 33 2471 800 fax : + 31 33 2459 220 e-mail : info@lennoxbenelux.com POLAND : LENNOX POLSKA Sp. z o. o. tel. : + 48 22 832 26 61 fax : + 48 22 832 26 62 e-mail : lennoxpolska@inetia.pl PORTUGAL : LENNOX CLIMATIZAÇAO LDA.
Need help?
Do you have a question about the ROOFTOP FLEXY FCA Series and is the answer not in the manual?
Questions and answers