ELECTRICAL DATA
MODBUS - BACNET
@
@
(hexa)
(deci)
01H
1
R/W
02H
2
R/W
10 = 1.0°c
03H
3
R/W
10 = 1.0°c
04H
4
R/W
1 = 1%
05H
5
R/W
10 = 1.0°c
06H
6
R/W
10 = 1.0°c
07H
7
R/W
10 = 1.0%
08H
8
R/W
10 = 1.0%
09H
9
R/W
0AH
10
R/W
0BH
11
R/W
0CH
12
R/W
0DH
13
R/W
0EH
14
R/W
0FH
15
R/W
10H
16
R/W
1 = 2001
11H
17
R/W
10 = 1.0°c
12H
18
R/W
10 = 1.0%
13H
19
R/W
10 = 1.0°c
14H
20
R/W
10 = 1.0%
15H
21
R/W
16H
22
R/W
17H
23
R/W
18H
24
R/W
19H
25
R/W
1AH
26
R/W
1BH
27
R/W
1CH
28
R/W
1DH
29
R/W
1EH
30
R/W
1FH
31
R/W
20H
32
R/W
21H
33
R
22H
34
R
10 = 1.0°c
23H
35
R
10 = 1.0°c
24H
36
R
10 = 1.0°c
25H
37
R
10 = 1.0°c
26H
38
R
10 = 1.0%
10 = 1.0
27H
39
R
28H
40
R
10 = 1.0%
Application Guide • FLEXY FX-AGU-1112-E
[ BMS ] Activation of the control by a computer or an automat - mode BMS is activated if
1 = 1 s
this value is different from zero, This value is decreased every second
[Occupation][Room SP] Required maximum room temperature in °C. Cooling set point
[Occupation][Room SP] Required minimum room temperature in °C. Heating set point
[Room SP] Required room minimum fresh air rate in % Middle of the dead zone.
[Inoccupation][Room SP] Required maximum room temperature in °C. Cooling set point
[Inoccupation][Room SP] Required minimum room temperature in °C. Heating set point
[Humidity] Desired Maximum relative humidity in Room (in %). – Dehumidifi cation set point.
[Humidity] Desired Minimum relative humidity in Room (in %). – Humidifi cation set point.
not used
not used
not used
1 = 1h
[Clock] Hour
1 = 1m
[Clock] Minute
1 = 1
[Clock] Day of the month
1 = 1
[Clock] Month
[Clock] Year
[BMS] Room temperature coming from the BMS
[BMS] Room humidity coming from the BMS
[BMS] Outdoor temperature coming from the BMS
[BMS] Outdoor humidity coming from the BMS
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
1 = 1
[Alarm] Code Error
[Temperature] Room
[Temperature] Outdoor
[Temperature] Supply
[Temperature] Return
[Relative Humidity] Room
[Absolute Humidity] Room
g/Kg
[Relative Humidity] Outdoor
CONTROL variables
DS50
3934
3322 (BMS)
3323 (BMS)
3312 (BMS)
3322 (Uno)
3323 (Uno)
3341 (BMS)
3342 (BMS)
3121
3122
3123
3124
3125
2824
2828
2814
2818
1000
2112
2111
2113
2114
2122
2124
2121
• 37 •