3. Connect the input point lead to the other terminal on the solid state relay; connector.
4. Connect the other end of the cable to the appropriate terminals on the input module. Be sure the
length of the annunciator cable does not exceed 10m (32.8ft).
5. Make sure the solid-state relay connector is fully seated on the power supply and tighten the
screws to secure it.
6. Close the power supply door.
7. Repeat this procedure for the second redundant power supply, if applicable.
8. Go to the next section
2.3.4

Connecting power

Use the appropriate portion of the following procedure to connect the power wiring to the redundant
power supply.
WARNING
Turn off power at the source of the supply before connecting to the power supply terminals.
Failure to do so could cause injury to personnel and/or equipment. This equipment must be
provided with a disconnect on each ungrounded conductor.
ATTENTION
1. 120/240 Vac Power
2. Open the door on the front of the redundant power supply.
3. Connect the high side of the Vac power line (black) to the L1 terminal on the power connector.
4. Connect the low side of the Vac power line (white) to the L2/N terminal.
Connecting
We recommend 14 AWG, 75°C, copper wire for power connections.
l
Torque screw terminals to 7 inch-pound (0.8 Newton-meter).
l
power.
- 17 -