Introduction; General Description; Special Features - Mitsubishi Electric MELSEC ST Series Installation Manual

Modular input/output system
Table of Contents

Advertisement

1

Introduction

The most important characteristics of the MELSEC ST series are summarized in this installation
description. This description is designed to help the experienced user quickly start-up the mod-
ules. Additional information and a detailed mounting and wiring description is in the MELSEC ST
series operating manual. This documentation is provided solely as a quick reference.

General Description

1.1
The MELSEC ST series is a modular input and output system which is connected as slave sta-
tion to a PROFIBUS/DP network. An ST series station consists of
b a head station to which the PROFIBUS is connected.
b Power supply modules.
b Digital and analog I/O modules.
The I/O modules can be combined as desired according to the requirements.

Special Features

1.2
Reduced wiring effort
External voltages
for supplying sensors and actuators are connected to the power distribution modules of
the ST series only. The other system modules are supplied with power via internal connec-
tions. Wiring requirements are significantly reduced because the supply voltage does not
need to be connected to each individual module.
PROFIBUS connection
Only the head station is connected to the PROFIBUS/DP network.
Connection of the I/O modules
Peripherals are connected either via spring clamp terminals, (into which the wires are just
inserted), or via conventional screw clamp terminals.
Flexible System Set-up
The number of inputs and outputs can be adapted easily to the application. Digital modules with
2, 4, and 16 inputs, and with 2 and 16 outputs are available. Up to 63 I/O modules (max. 26 ana-
log I/O modules) can be connected to one head module.
Simple Service
The electronics modules are plugged into a base module to which the peripheral signals are
connected. The base module is mounted on a DIN rail. Electronic modules can be replaced in
operation. No tool is required to do this. The GX Configurator DP is available to configure the
system.