Summary of Contents for KBR multisys D2-ESET/MSMT-4
Page 1
User Manual Technical Parameters Interfaces for KBR eBus and module bus multisys D2-ESET/MSMT-4 multisys D2-BSET-4 You will find the relevant instructions for KBR System English devices in our Download Center. https://www.kbr.de/de/dienstleistungen/ download-center...
Page 2
Table of contents KBR Kompensationsanlagenbau GmbH does not accept any liability for any loss or dam- age resulting from printing errors in or changes to this manual. In addition, KBR Kompensationsanlagenbau GmbH does not accept any liability for any loss or damage caused by defective devices or devices manipulated by the user.
Introduction Introduction Thank you for choosing this KBR quality product. To become familiar with the operation and programming of the device and to use the full range of functions of this high-quality product at all times, you should read this user manual carefully.
Introduction Safety keys This manual contains instructions that you must follow for your personal safety and to avoid material damage. These instructions are identified by a warning sign or information symbol, depending on the degree of hazard they warn about. DANGEROUS VOLTAGE "Warning"...
Introduction Safety notes In order to prevent operating errors, device operation is kept as simple as possible. This will enable you to start your device up quickly. It is in your own interest to read the following safety instructions carefully. The applicable DIN/VDE regulations must be observed during installation! Power supply connection, setup and operation of the device must be performed by qualified personnel only.
Each device undergoes a long-term test before delivery. With regard to product liability, please see our general terms and conditions for electronic devices, which you can read at www.kbr.de. The warranty on device characteristics only applies if the device is operated in...
- Modbus On the Energy Bus side it acts as master and on the Ethernet side it acts as slave. The two interfaces (RS-485 on the KBR eBus side, and Ethernet on the network side) are galvanically separated. The multisys D2-BSET-4 connects the KBR module bus to your computer through an Ethernet connection.
Connection diagram Both variations are described below. Connection diagram R 12 zu weiterenTeilnehmern Modulbus bzw. Leitungsabschluss / to other bus devices and line termination Modulbus/ Module bus multisys multisys D2-BSET-4 D2-ESET/MSMT-4 V4.00...
Interfaces LAN and KBR eBus RS-485 Hardware Configuration RS485 Interface and LAN The RS-485 interface is set to the KBR eBus parameters 38,400 baud, 8 data bits, parity even, 1 stop bit. If necessary, it can be terminated using four DIP switches. RS485 RS-485 (3-pole multi-pin connector, 3.5 mm)
Interfaces LAN and KBR module bus LAN and KBR Module Bus Interfaces (multisys D2-BSET-4) The Modbus interface is set to the Modbus parameters 38,400 baud, 8 data bits, parity even, 1 stop bit. If necessary, it can be terminated using four DIP switches.
IOT ePort E20 Software configuration Configuration is carried out using the IOT Service Tool. Supplier: www.hi-flying.com/download-center-1/applications-1/download-item-iotservice After installing and starting the IOT Service Tool, the connected network is scanned and the e-ports found are displayed, and can be further processed. After selecting the e-port, click on „Config“...
IOT ePort E20 Assigning an IP Address to a Device of which the Address is Not in the Address Range of the Network In the main window of the IOT Service Tool, open the ‘BroadCast Scan’ window via Setting (C) -> BroadCast. E-port devices that are in the network but do not have a valid network address are listed here.
Page 14
IOT ePort E20 After selecting the e-port, click on „Config“ to access the configuration settings. V4.00...
IOT ePort E20 4.2. E-port Configuration for eBus TCP For eBus TCP, the parameters must be set as shown in the figure below. The network parameters (IP address, mask, gateway, DNS) must be adapted to local circumstances. NOTE - „Flow Control: Half Duplex“ controls the changeover of RS-485 components. - The local port must be set to 8000 - Click „Confirm“...
Page 16
IOT ePort E20 When „Detail“ is selected, this window appears: NOTE - For eBus TCP, the UART protocol must be set to ‘NONE’ - The gap time should be set to 10 (ms). (This is the waiting time after serial reception, until a telex message is sent via the network).
IOT ePort E20 4.4. E-port configuration for Modbus TCP For Modbus TCP, the parameters must be set as shown in the figure below. The network parameters (IP address, mask, gateway, DNS) must be adapted to local circumstances. NOTE The UART parameters must be adapted to the local bus parameters. Local port: 502 Several connections to a serial interface, via the TCP, are possible.
Page 19
IOT ePort E20 NOTE Modbus ASCII cannot be configured. Several connections to a serial interface, via the TCP, are possible. Replies are only sent to the enquirer. V4.00...
Connection For proper operation, material use shielded twisted-pair cables only; e.g. I-Y(St)Y 2x2x0.8 BUS connection Pins for Device multisys D2-ESET/MSMT-4 BUS connection Terminal 90 ( ) via RS-485 Terminal 91 (A) Terminal 92 (B) BUS connection 6 pole modular cable, multisys D2-BSET-4 RJ-12 connector: 6P6C max.
Technical Data Standards and miscellaneous DIN EN 60721-3-3:1995-09 + DIN EN 60721-3-3/A2:1997-07; Standards 3K5+3Z11; (IEC721-3-3;3K5+3Z11) Operating tem- Ambient K55 (-5°C … +55°C) perature conditions Air humidity 5% …. 95% Storage -25°C … +70°C temperature Operating height 0 … 2,000 m above sea level DIN EN 61010-1:2011-07;...