Conventional 24Vac Thermostat Control Wiring Connections - Rheem A17 Series Installation Instructions Manual

Air cooled condensing units
Table of Contents

Advertisement

4.9 Control Wiring (cont.)
IMPORTANT:
system requires continuous 18 AWG thermostat
wire. DO NOT use phone cord to connect indoor
and outdoor units. This will damage the controls.
The EcoNet™ control system requires four (4) control
wires for unit operation:
R 24 VAC
C 24 VAC common
Data wire E1 Communications
Data wire E2 Communications
The EcoNet™ enabled air handler or furnace is
equipped with a 24-volt, 40 or 50 VA transformer
for proper system operation. See the wiring
diagram below for low voltage wiring connections.
Control Center
E1
E2
R
C
Indoor
Unit
BR/W
E1
PR
E2
R
R
BR
C
These wires need to be connected to each device
(Control Center, indoor air handler or furnace, and
outdoor unit).
Once all devices are connected, apply the line
voltage to the indoor and outdoor units.
When all devices are powered, the EcoNet™
Control Center should detect the indoor and
outdoor units within 45 seconds.
Once the system is powered and all components
are communicating with each other, the airflow
settings will be automatically configured in the air-
handler or furnace.
All adjustments for indoor airflow are made at the
EcoNet™ Control Center from this point for variable
speed air-handlers and furnaces. Air-flow adjustment
on (-)H2T air-handlers must be made by moving the
low voltage leads on the motor terminal block. Items
that can be changed are for variable speed
air-handlers and furnace (except (-)H2T air-handlers)
airflow trim adjustment, on-demand dehumidification,
cooling and heating airflow and electric heat airflow.
The Control Center also has a wide range of fault and
history information. To access any of the control center
menus press the settings, status, or service icons
at the bottom of the touch screen. Refer to the
air handler or furnace installation manual and
the EcoNet™ Control Center installation manual
for further details on setting up the system and
available adjustment options.
The EcoNet™ control
Outdoor
Unit
Y/PK
E1
O/WH
E2
R
R
BR
C
4.0 INSTALLATION
4.9.4 Conventional 24VAC
Thermostat Control Wiring
Connections
The (-)A17 series condensing units allow the installer
to use conventional 24 VAC control wiring and a
conventional 2-stage thermostat.
IMPORTANT:
for unit installation and operation is by the EcoNet™
Communicating System which allows access to
the fault history of the system. This diagnostic
information is not available at the thermostat when
the (-)A17 unit is using a conventional thermostat.
Thermostat control wiring requires a minimum of
six (4) wires for proper unit operation:
R - 24 VAC
C - 24 VAC common
Y1 - First-stage cooling operation
Y2 - Second-stage cooling operation
The following figures show the typical control
wiring diagram with (-)A17 condensing unit using a
conventional 24VAC 2-stage thermostat. The
cooling airflow level will need to be adjusted
for homeowner comfort once the system is
operational. Use DIP switches on the air-handler
or furnace control board to adjust indoor air-flow.
Speed changes on (-)H2T air-handlers must be made
on the motor terminal block.
WIRE COLOR CODE
BK - BLACK
GR - GREY
BR - BROWN
O - ORANGE
BL - BLUE
PR - PURPLE
G - GREEN
R - RED
TYPICAL 2-STAGE THERMOSTAT: (-)A17 AIR CON-
DITIONER WITH ELECTRIC HEAT USING A TWO-
STAGE THERMOSTAT WITH DEHUMIDIFICATION
Typical Two-Stage Thermostat
Y1 Y2
Air Handler
W/BK
W1
W/BL
W2
Y
Y1
Y/BL
Y2
R
R
BR
C
G
G
ODD
** ODD non-funtional on (-)H2T air-handlers
Field-Installed
Factory Standard
The preferred method
W - WHITE
Y - YELLOW
G
W2 C
R DHM
W1
Outdoor Unit
Y
Y1
Y/BL
Y2
R
R
BR
C
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

A1724aj2cbA1736aj2cbA1748aj2cbA1760aj2cb

Table of Contents