ENERGY SAVING
Fig. 7.4: Changing the motor body position
Procedure (Fig. 7.4):
1. Slacken and remove the four screws M5 holding the motor.
2. Turn the motor to the desired position without extracting it from the pump housing.
3. Insert and tighten the pump housing screws (The tightening torque of the screws of the
pump housing must correspond to a value of 3.3 ± 0.5 Nm).

7.4 Insulation of pump housing

Fig. 7.5: Insulation of pump housing
The heat loss from the pump and pipework can be reduced by insulating the pump housing and the
pipe with the thermal insulation shells supplied with the circulator (supplied as standard only with
model ES2 ADAPT) → Fig. 7.5.
The thermal insulation shells can be ordered separately.
Do not insulate the control box or cover the control panel.
CAUTION
Installation at Site
16