10. Compounds used on threaded joints of gas piping shall
be resistant to action of liquefied petroleum gases.
11. Purge air before lighting unit by disconnecting pilot at
outlet of pilot valve. In no case should line be purged into
heat exchanger.
12. After installation, the piping system must be checked for
leaks. Use soap solution.
13. Install a ground joint union and a gas cock upstream of
the unit for easy servicing of controls, including a 1/8"
NPT plugged tapping accessible for test gauge
connection (see Figure 6).
T T a a b b l l e e 2 2 – – G G a a s s P P i i p p e e C C a a p p a a c c i i t t i i e e s s
In Cu. Ft. per Hour with Pressure Drop of 0.3 in. W.C. with Specific Gravity 0.60
L L e e n n g g t t h h
o o f f P P i i p p e e
i i n n F F t t . .
1 1 / / 2 2
1 1 5 5
76
3 3 0 0
73
4 4 5 5
44
6 6 0 0
50
7 7 5 5
9 9 0 0
1 1 0 0 5 5
1 1 2 2 0 0
1 1 5 5 0 0
1 1 8 8 0 0
2 2 1 1 0 0
2 2 4 4 0 0
2 2 7 7 0 0
3 3 0 0 0 0
4 4 5 5 0 0
6 6 0 0 0 0
T T a a b b l l e e 3 3 – – S S p p e e c c i i f f i i c c G G r r a a v v i i t t y y C C o o n n v v e e r r s s i i o o n n
F F a a c c t t o o r r s s
Multiplying factors to be used with Table 2 when
the specific gravity of gas is other than 0.60.
N N A A T T U U R R A A L L G G A A S S
S S p p e e c c i i f f i i c c
S S p p e e c c i i f f i i c c
F F a a c c t t o o r r
G G r r a a v v i i t t y y
G G r r a a v v i i t t y y
0.55
1.04
0.60
1.00
0.65
0.962
W W i i r r i i n n g g
!
CAUTION
Disconnect power supply before making wiring connections
to prevent electrical shock and equipment damage. ALL
UNITS MUST BE WIRED STRICTLY IN ACCORDANCE
WITH WIRING DIAGRAM FURNISHED WITH UNIT.
ANY WIRING DIFFERENT FROM WIRING DIAGRAM MAY
BE HAZARDOUS TO PERSONS AND PROPERTY.
Any damage to or failure of Modine units caused by incorrect
wiring of the units is not covered by MODINE'S STANDARD
WARRANTY (see inside Back Cover).
8 8
3 3 / / 4 4
1 1
1 1 - - 1 1 / / 4 4
218
440
750
152
285
590
124
260
435
105
200
400
97
190
345
88
168
320
80
160
285
158
270
128
242
120
225
205
190
178
170
140
119
P P R R O O P P A A N N E E G G A A S S
F F a a c c t t o o r r
1.50
0.633
1.53
0.626
1.60
0.612
14. Allow at least 5 feet of piping between any high pressure
regulator and unit controls.
15. Testing Piping System. The appliance and its individual
shutoff valve must be disconnected from the gas supply
piping system during any pressure testing if the test
pressure is in excess of 1/2 psi.
The appliance must be isolated from the gas supply
piping system by closing its field installed manual shutoff
valve.
D D i i a a m m e e t t e e r r o o f f P P i i p p e e — — I I n n c c h h e e s s
1 1 - - 1 1 / / 2 2
2 2
1220
2480
6500
890
1650
4700
700
1475
3900
610
1150
3250
545
1120
3000
490
930
2600
450
920
2450
420
860
2300
380
710
2000
350
720
1950
320
660
1780
300
620
1680
285
580
1580
270
545
1490
226
450
1230
192
380
1030
F F i i g g u u r r e e 6 6 – – R R e e c c o o m m m m e e n n d d e e d d P P i i p p i i n n g g t t o o C C o o n n t t r r o o l l s s
SUPPLY LINE
GAS
SUPPLY LINE
3"
MIN.
SEDIMENT
All field installed wiring must be done in accordance with the
National Electrical Code ANSI/NFPA 70 — Latest Edition or
Canadian Electrical Code CSA C22.1 Part 1 or local codes.
Unit must be electrically grounded according to these codes.
See wiring diagram shipped with unit.
The power to these duct furnaces should be protected with a
fused disconnect. Units for use with three-phase electric
power must be provided with a motor starter having properly
sized overload protection.
Location of thermostat should be determined by heating
requirements and be mounted on an inside wall about 5'
above floor level where it will not be affected by heat from the
unit or other sources, or drafts from frequently opened doors.
See instructions packed with thermostat.
3 3
4 4
6 6
13880
38700
9700
27370
7900
23350
6800
19330
6000
17310
5400
15800
5100
14620
4800
13680
4100
12240
4000
11160
3700
10330
3490
9600
3250
9000
3000
8500
2500
7000
2130
6000
GAS
GROUND
JOINT
UNION
W/ BRASS
GAS
SEAT
COCK
TO
CONTROLS
PLUGGED
1/8" NPT TEST
GAGE CONNECTION
TRAP
8 8
79000
55850
45600
39500
35300
32250
29850
27920
25000
22800
21100
19740
18610
17660
14420
12480