System 6
3-tank solar system with pump logic and priority logic
The controller compares the temperature at sensor
S1 to the temperatures at sensors S2, S4 and S5. If the
measured temperature differences are higher than the
adjusted switch-on temperature differences, the pump
22
(R1, R2 and/or R3) will be activated and the corre-
sponding tank will be loaded up to the adjusted maxi-
mum temperature at most. Priority loading or parallel
loading can be carried out in this system.
Sensor/
Designation
Description
terminal
S1
TCOL
Temperature collector
S2
TST1B
Temperature tank 1 bottom
S3
Optional sensor for measure-
ment purposes or options
S4
TST2B
Temperature tank 2 bottom
S5
TST3B
Temperature tank 3 bottom
V40
Optional sensor for measure-
ment purposes or options
Relay
Description
R1
Solar pump tank 1
R2
Solar pump tank 2
R3
Solar pump tank 3
R4
optional:
Thermal disinfection
Parallel relay
Heat dump