COMMUNICATION SETTINGS
Drive Number
Baud Rate
Serial Link No.
Fast Scan Anal 1
Fast Scan Anal 2
Fast Scan Anal 3
Fast Scan Update
SYSTEM PARAMETER SETTINGS
Line Voltage
VT Primary
VT Secondary
Motor FLC
CT Primary
E/F CT Primary
Earth fault Alarm
"
"
" Delay
Earth Fault Trip
"
"
" Delay
Current Inhibit
Start/Stop Signal
Starting Method
Max Time in Star
Transition Time
Star to Delta at
Low Speed FLC
Low Speed t6X
Designate Aux 1
Aux 1 Delay
Designate Aux 2
Aux 2 Delay
Protection Only
VOLTAGE SETTINGS
Undervoltage Setting
Undervoltage Delay
Undervoltage Restart
Undervoltage Restart Delay
Overvoltage Alarm
Overvoltage Trip
Overvoltage Trip Delay
CURRENT SETTINGS
Maximum Start Time
Number of starts
Start Period
Start Inhibit Time
Undercurrent Alarm
Undercurrent Alarm Delay
Undercurrent Trip
Undercurrent Trip Delay
Load Increase Alarm
Low Set Overcurrent
Low Set Overcurrent Delay
High Set Overcurrent
High Set Overcurrent Delay
Overload Setting
Thermal Capacity Alarm
t6x Time
Hot/Cold Ratio
Cool Time Factor
Stall Time Factor
Overload reset Method
Unbalance Current
Current Unbalance Maximum Time
Page 28
1 - 320
110,300,1200,2400,4800,9600,19200
1 - 33
0 - 201
0 - 201
0 - 201
0 - 30s
100v-22kv
Not Connected, 100v-22kv
"
" , 95-660v
1-2500A
1-2500A
1-2500A
1-100% Inom
1-60 Sec
1-100% Inom
0-2 Sec
off, 400-1000% FLC
Momentary, Maintained
DOL,Star/Delta,Reversing
2 Speed,Circuit Breaker
1-60 Sec
0.05-2.0 Sec
40-200% FLC
1-2000A
0.5-120Sec
Alarm,Contactor A, Contactor B, Run
0-120 Sec
Trip, Trip Fail Safe, Contactor A,
Contactor B
0-120 Sec
Yes, No
50-95%
0.2-10 Sec
Yes,No
0.2-120 Seconds
100-120%
100-120%
1-100 Sec
1-250 Sec
1-10
1-60 Min
1-60 Min
10-90% FLC
1-60 Sec
10-90% FLC
1-60 Sec
60-150% FLC
100-500% FLC
0.5-10 Sec
400-1200% FLC
Inst-4 Sec
60-130% FLC
50-99%
0.5-120 Sec
20-100%
1-15
20-100%
Auto,Hand
10-40%
20-120 Sec
Issue 2 22/4/98
0
9600
33
0
1
2
0
415v
Not Connected
"
"
100A
100A
100A
5% Inom
10 sec
10% Inom
0.5 Sec
off
Momentary
DOLNR
10 Sec
0.2 Sec
150% FLC
10A
10 Sec
Alarm
0
Trip
0
No
80%
5 Sec
No
115%
120%
1 Sec
10 Sec
10
30 Min
30 Min
50%
2 Sec
40$
5 Sec
120%
400%
2.0 Sec
800%
Inst
105%
80%
10 Sec
50%
5
50
Hand
15%
30 Sec
MPC2000D