10 Supplement

10.1 Technical data

Note for approved instruments
The technical data in the respective safety instructions are valid for approved instruments (e.g. with
Ex approval). In some cases, these data can differ from the data listed herein.
All approval documents can be downloaded from our homepage.
General data
Series
Weight
Housing material
Connection terminals
Ʋ Type of terminal
Ʋ Wire cross-section
HART communication sockets
Voltage supply
Operating voltage
Ʋ Nominal voltage AC
Ʋ Nominal voltage DC
Max. power consumption
Sensor input
Number of sensors
Input type
Terminal voltage
Off-load voltage
Short-circuit current
Residual ripple
Processing circuit
Quantity
Type of output
Off-load voltage
Residual ripple of the output current
Current on the input in case of short-
circuit
Current without connected sensor
Ʋ In the range of +20 ... +60 °C
(+68 ... +140 °F)
Ʋ In the range of -20 ... +20 °C
(-4 ... +68 °F)
VEGATRENN 141 •
Module unit for mounting on carrier rails 35 x 7.5 acc. to
EN 50022/60715
160 g (5.14 oz)
Polycarbonate PC-FR
Screw terminal
0.25 mm² (AWG 23) ... 2.5 mm² (AWG 12)
ø 2 mm
24 ... 230 V (-15 %, +10 %) 50/60 Hz
24 ... 65 V (-15 %, +10 %)
2 W (10 VA)
1 x 4 ... 20 mA/HART (5 x HART multidrop)
Active (sensor power supply by VEGATRENN 141)
21 ... 16.5 V DC at 4 ... 20 mA
24 V DC (+/- 1 V)
< 26 mA
< 50 mV RMS
1 x 4 ... 20 mA/HART
Active
< 15.5 V DC
< 50 µA RMS
< 10 µA
< 50 µA
< 200 µA
10 Supplement
19