Parameters
2.1
Parameters
Table 2-1
Parameters for analog output module
2AO I HF
Group diagnostics (parameter
assignment error, internal error)
Diagnostics: Wire break
Response to CPU/master STOP
Type/range of output
Substitute value
2
No diagnostics detection between -1.1852 mA and +1.1852 mA.
1
If there is no voltage being supplied to the interface module or COMPACT module but the supply to the analog output
2
modules continues, the substitute values that have been assigned parameters are output. Substitute values must be within
the nominal range. You can assign values from -27,648 to +27,648 as parameters (when assigning parameters using the
GSD file).
2AO I HF analog electronic module (6ES7135-4MB02-0AB0)
Manual, 04/2007, A5E01076972-01
Range of values
Disable
•
Enable
•
Disable
•
1
Enable
•
No output current or
•
voltage
Substitute a value
•
Keep last value
•
Deactivated
•
4 to 20 mA
•
± 20 mA
•
To 65,535 (value range must
lie within the nominal range)
Default setting
Disable
Disable
No output current or
voltage
4 to 20 mA
± 20 mA: 0 mA
4 mA to 20 mA 4 mA
2
Applicability
Module
Channel
Module
Channel
Channel
13