1.1 2AO I HF analog electronic module (6ES7135-4MB02-0AB0)
Crosstalk between the outputs
Operational limit (in the entire temperature range,
with reference to the output range)
Basic error limit (operational limit at 25°C with
reference to output range)
Temperature error (with reference to the output
range)
Linearity error (with reference to the output range) ±0.01% (for resistive load)
Repeatability
(in steady state at 25°C with reference to output
range)
Output range (rated value)
Load impedance (in the rated range of the output)
Current output
Destruction limit against voltages/currents applied
from outside
Connection of actuators
10
For current outputs
For inductive load
Open circuit voltage
Voltage at the outputs to M
Current
Current output two-wire connection
Suppression of interference, limits of error
< -60 dB
± 0,1 %
± 0,05 %
±0.003%/K
± 0,01 %
Transmitter selection data
± 20 mA
4 mA to 20 mA
Max. 500 Ω
1 mH
18 V
Max. 15 V continuous; 75 V for max. 1 ms
ANA
(sampling ratio 1:20)
Max. 50 mA DC
Supported
2AO I HF analog electronic module (6ES7135-4MB02-0AB0)