GENERAL INFORMATION
WARNING: This product is not intended for use in industrial
factories or commercial parking garages.
Detector Description
• Listed to UL standard 2075
CO sensitivity is evaluated to UL 2034
• Supervised
• Local sounder
• Dual LED's
• Test/Hush button
• Surface mount to wall or ceiling
• Optional drywall anchors included
INSTALLATION AND SETUP GUIDE
5800CO Carbon Monoxide Detector
with Built-in Wireless Transmitter
Table 1: Detector LED Modes
Green LED
Normal (standby)
Blinks every
10 seconds
Alarm/Test
Off
Low Battery
Off
Detector Trouble
Off
Detector End-of-
Off
Life
Power Up
Blinks every
10 secs
(w/red LED)
††
Red LED
Sounder
Off
Off
Blinks every
Temporal 4
1 second
Pattern
Blinks every
Chirp every 45
45 seconds
sec beginning 7
for 37 days
days after LED
blinks, continues
30 days
Blinks every
One chirp every
5 seconds
45 seconds
Blinks every
One chirp every
10 seconds
45 seconds
Blinks every
Off
††
††
10 secs
(w/green LED)
†