Remote Mount - Emerson THUM Quick Start Manual

Wireless adapter
Table of Contents

Advertisement

Quick Start Guide
5

Remote mount

Prerequisites
Install the HART device according to standard installation practices and the
manufacturer's instructions, being sure to use an approved thread sealant
on all connections.
Procedure
1. The THUM Adapter should be mounted as shown in
Figure 5-1: Remote Mount
2. Ground the Remote Mount Kit per local practices.
3. Connect the THUM Adapter to the wired device using standard
practices. Wire running from the THUM Adapter to the wired device
should be shielded or in conduit when installed in electrically noisy
environments.
4. Connect the THUM Adapter to the HART wired device using the
Wiring
5. Close the housing cover on the HART wired device, so that metal
touches metal, but do not overtighten to prevent damaging the unit.
Note
Two splice connectors are included with the THUM Adapter. The first
is a two connection splice. The second is a three connection splice for
use with a resistor, if there is not enough resistance in the loop. Both
of these splice connectors can accept 14 to 22 gauge wire. See wired
device reference manual for information on the required loop
resistance.
10
diagrams.
September 2020
Figure
5-1.
Emerson.com/Rosemount