Download Print this page

Specifications; Blower Motor - Amana American Pride ACNF Series Manual

Ceiling-mount air handlers

Advertisement

S
PeCiFiCAtioNS
Performance Ratings
Cooling (BTU/h)
Airflow Rate CFM (High/ Low)¹
Blower
Diameter
Width
Coil Drain Connect FPT
Refrigerant Line Connection Size
Liquid
Suction
Electrical Data
Voltage
Min Circuit Ampacity @ 230V
Min Circuit Ampacity @ 208V
Max. Overcurrent Device @ 230V
Max. Overcurrent Device @ 208V
Minimum Voltage VAC
Maximum Voltage VAC
Electric Heat
kW @ 230 Volts
BTU/h @ 230 Volts

Blower Motor

FLA
HP
Ship Weight (lbs)
¹ CFM @ .2 static
Note: When the room thermostat calls for second stage heat, the first stage (heat pump) operation must be locked out. When matching the "AC" unit that
has electric heat with a heat pump, order "HEAT PUMP SHUT OFF KIT HPSK-01." The ACXX-00 units do not require this kit.
SS-AACNF
ACNF18
ACNF18
ACNF18
001
051
061
18,000
18,000
18,000
660/595
660/595
660/595
5.75
5.75
5.75
6.75
6.75
6.75
3/4"
3/4"
3/4"
⅜"
⅜"
⅜"
¾"
¾"
¾"
208/230
208/230
208/230
0.9
27
33.5
0.9
23.5
29.2
15
30
35
15
25
30
197
197
197
253
253
253
0.0
4.8
6.0
0
16,400
20,500
0.72
0.72
0.72
1/8
1/8
1/8
54
57
57
www.amana-hac.com
P
roduCt
ACNF18
ACNF24
ACNF24
081
001
051
18,000
24,000
24,000
660/595
880/840
880/840
5.75
6.31
6.31
6.75
8.25
8.25
3/4"
3/4"
3/4"
⅜"
⅜"
⅜"
¾"
¾"
¾"
208/230
208/230
208/230
40.6
1.68
27.8
35.3
1.68
24.3
45
15
30
40
15
25
197
197
197
253
253
253
7.3
0.0
4.8
24,900
0
16,400
0.72
1.34
1.34
1/8
1/4
1/4
57
61
64
S
PeCiFiCAtioNS
ACNF24
061
24,000
880/840
6.31
8.25
3/4"
⅜"
¾"
208/230
34.3
29.9
35
30
197
253
6.0
20,500
1.34
1/4
64
3

Advertisement

loading

This manual is also suitable for:

American pride acnf18001American pride acnf18051American pride acnf18061American pride acnf18081American pride acnf24001American pride acnf24051 ... Show all