S+S Regeltechnik PREMASGARD 111 Series Operating Instructions, Mounting & Installation page 6

Hide thumbs Also See for PREMASGARD 111 Series:

Advertisement

G
®
PREMASGARD
Schematic diagram*
Output:
4...20 mA
LED
min. max.
ON
1 2 3 4 5 6
Offset
DIP
switches
Plug for
display
1 2 3
*
Connection
:
2-wire connection for devices with ⁄ without display (not illuminated)
3-wire connection for devices with illuminated display
Conversion table for pressure values:
Unit =
1 Pa
1 kPa
1 bar
1 mbar
1 mH
O
0.0980665 bar
2
DIP switches for
pressure range setting, output attenuation and zero compensation:
Pressure range
(selectable, max. measuring range is depending to the type of device)
0...1000 Pa
0...5000 Pa
0...10000 Pa
0...100 Pa
0...1000 Pa
0...300 Pa
0...2000 Pa
0...500 Pa
0...3000 Pa
0...1000 Pa
0...5000 Pa
0...10000 Pa
Measuring range mode
(Mode selectable)
Unidirectional ( 0 ...+MR )
Bidirectional (–MR ...+MR )
111x ⁄ 112x ⁄ 112x - SD
PREMASGARD
PREMASGARD
®
PREMASGARD
112x - SD - I
Pushbutton
Zero point setting
(auto zero)
Offset correction
auto
zero
see graph
ca.± 10% of
Offset
final value
Plug for display
contact is
on the right side
DIP switch 6
is not assigned!
bar
0.00001 bar
0.01 mbar
0.01 bar
1 bar
1000 mbar
0.001 bar
98.0665 mbar
–1000...+1000 Pa
0...4000 Pa
–100...+100 Pa
0...6000 Pa
–300...+300 Pa
0...8000 Pa
–500...+500 Pa
–1000...+1000 Pa
Output characteristic line
DIP 3
(Mode selectable)
OFF
Linear
O N
Square root extracting
®
111x - I
Schematic diagram
®
112x - I
Output:
0 -10 V
min. max.
Offset
Plug for
display
mbar
1 Pa
10 mbar
1000 Pa
100000 Pa
1 mbar
100 Pa
9806.65 Pa
–5000...+5000 Pa –10000...+10000 Pa
–1000...+1000 Pa
–4000...+4000 Pa
–2000...+2000 Pa
–6000...+6000 Pa
–3000...+3000 Pa
–8000...+8000 Pa
–5000...+5000 Pa
–10000...+10000 Pa
13
PREMASGARD
LED
ON
1 2 3 4 5 6
auto
DIP
zero
switches
Offset
1 2 3
Pa
kPa
0.001 kPa
1 kPa
100 kPa
0.1 kPa
9.80665 kPa
DIP 1
DIP 2
OFF
OFF
O N
OFF
OFF
O N
O N
O N
Measurement signal filtering
DIP 4
(Time interval selectable)
OFF
Long (10 s)
O N
Small (1 s)
Rev. 2018 - V14
®
PREMASGARD
111x - U
PREMASGARD
®
112x - U
®
112x - SD - U
Pushbutton
Zero point setting
(auto zero)
Offset correction
see graph
ca.± 10% of
final value
Plug for display
contact is
on the right side
DIP switch 6
is not assigned!
mH
O
2
0.000101971 mH
O
2
0.101971 mH
O
2
10.1971 mH
O
2
0.0101971 mH
O
2
1 mH
O
2
DIP switch 6
is not assigned!
DIP 5
OFF
O N