Hook-Up - Rheem H2AC Installation Instructions Manual

Featuring esync integration technology
Table of Contents

Advertisement

TABLE 5
COPPER
WIRE SIZE—AWG
UNIT
MCA
SUPPLY WIRE LENGTH—FEET
50
100
150
20
10
8
6
25
10
8
6
30
8
6
4
35
8
6
4
40
8
6
4
45
8
4
3
50
6
4
3
60
6
4
2
70
4
3
2
80
4
3
1
90
3
2
1/0
100
3
2
1/0
110
2
1
2/0
125
1
1
2/0
150
1/0
1/0
3/0
175
2/0
2/0
4/0
14
CONDUIT SIZE
1/2
HOLE SIZE
7/8
NOTES:
1. DETERMINE REQUIRED WIRE SIZE FROM MINIMUM CIRCUIT AMPACITY SHOWN IN INSTALLATION & OPERATING INSTRUCTION.
2. BOTTOM POWER ENTRY WILL NOT ACCOMMODATE WIRE LARGER THAN #2 AWG (SHADED AREA).
FIGURE 14
TYPICAL THERMOSTAT WIRING
TERMINAL BLOCK
22
Select the equivalent aluminum wire size from the tabulation below:
Splice copper wire pigtails to aluminum wire with U.L. recognized connectors for copper-
aluminum splices. Please exercise the following instructions very carefully to obtain a
positive and lasting connection:
1. Strip insulation from aluminum conductor.
2. Coat the stripped end of the aluminum wire with the recommended inhibitor, and wire
brush the aluminum surface through inhibitor. INHIBITORS: Brundy-Pentex "A";
Alcoa-No. 2EJC; T & B-KPOR Shield.
3. Clean and recoat aluminum conductor with inhibitor.
4. Make the splice using the above listed wire nuts or split bolt connectors.
5. Coat the entire connection with inhibitor and wrap with electrical insulating tape.
B. HOOK-UP
To wire unit, refer to the following hook-up diagram.
Refer to Figure 13 for location of wiring entrances.
Wiring to be done in the field between the unit and devices not attached to the unit, or
FIGURE 13
BASE ENTRY LOCATIONS
200
250
300
4
4
4
4
4
3
4
3
2
3
2
1
3
2
1
2
1
1/0
2
1
1/0
1
1/0
2/0
1/0
2/0
3/0
1/0
2/0
3/0
2/0
3/0
4/0
2/0
3/0
4/0
3/0
4/0
250
3/0
4/0
250
4/0
250
300
250
300
350
12
10
8
1/2
1/2
3/4
7/8
7/8
1-31/32
ONLY USED
ON DUAL
FUEL OR HEAT
PUMP
LOW VOLTAGE
MODELS
THERMOSTAT CONNECTIONS
R Y1 Y2 G C W1 W2 W3 B
HEAT
POWER
COOL
st-A1125-12-00
RUN THERMOSTAT
WIRING IN THIS
CHASE TO CONTROL
BOARD
POWER WIRES
FROM DISCONNECT
TO TERMINAL BLOCK
WASHERS
CONTROL VOLTAGE
KNOCKOUT
WIRE FROM
ZONE THERMOSTAT
STRAIGHT CONDUIT
FITTING
CONDUIT FROM
ZONE THERMOSTAT
WIRE SIZE, AWG
6
4
3
1
1
1-1/4
1-23/64
1-23/64
1-23/32
EXTERNAL MANUAL GAS
SHUT-OFF VALVE
SIZED PER CHART
OR USE KNOCK OUT
WIRE SIZE FROM
MIN. CIRCUIT AMPACITY
STRAIGHT CONDUIT
FITTING SIZED
PER CHART
CONDUIT FROM
POWER SUPPLY
SIZED PER CHART
2
1
0
1-1/4
1-1/2
1-1/2
1-23/32
1-31/32
1-31/32
CUT HOLE
GAS LINE
ST-A1125-10
00
000
2
2
2-15/32
2-15/32