1. Figure 1. SET-1000 level switch – features SET-1000 can be used as a controller of a level sensor located in potentially explosive atmosphere (zone 0,1 or 2) due to intrinsically safe inputs of the device. The SET-1000 itself must be installed in a non- hazardous area.
D15233FE-2 Installation and Operating Instructions INSTALLATION The SET-1000 can be wall-mounted. The mounting holes are located in the base plate of the enclosure, beneath the mounting holes of the front cover. The connectors of the external conductors are isolated by separating plates.
If the sensor cable must be extended or there is need for equipotential grounding, it can be done with the cable junction box. The cabling between the SET-1000 control unit and the junction box should be done with a shielded twisted pair instrument cable.
If the sensor cable must be extended and there is a need for equipotential grounding, it should be done with the junction box LJB2. The cabling between the SET-1000 control unit and the junction box should be done with a shielded twisted pair instrument cable.
D15233FE-2 Installation and Operating Instructions OPERATION AND SETTINGS The SET-1000 control unit is initialized at the factory as follows. See a more detailed description in chapter 3.1 Operation. Channel 1 Alarm takes place when the level hits the sensor (high level alarm)
Trigger point of an alarm in the sensor’s sensing element. Trigger level Sensor selection SET/DM3AL sensor or other Labkotec SET series sensor. Buzzer The buzzer can be disabled. The following tasks must only be executed by a person with proper education and knowledge of Ex-i devices.
3.4 Connect the wire back to the connector. If the problem can not be solved with the above instructions, please contact Labkotec Oy’s local distributor or Labkotec Oy’s service. Attention ! If the sensor is located in an explosive atmosphere, the...
In case of queries, please contact Labkotec Oy’s service. SAFETY INSTRUCTIONS SET-1000 level switch must not be installed in explosive atmosphere. Sensors connected to it may be installed in explosive atmosphere zone 0,1 or 2. In case of installations in explosive atmospheres the national requirements and relevant standards as IEC/EN 60079-25 and/or IEC/EN 60079-14 must be taken into account.
When installing the device, make sure that the electrical values of the cable between SET-1000 and sensor never exceed maximum electrical parameters. The cabling between SET-1000 control unit and cable extension junction box / cable joint must be executed as in figure 4 / 8 Extension cable should be shielded paired twisted instrument cable.
Need help?
Do you have a question about the SET-1000 and is the answer not in the manual?
Questions and answers