Code
MT
REC
P24652
REC
GENERAL DESCRIPTION
- Device with programmable differential relay with self-reclosing system. Symbol
- It has 2 independents outputs by relays. Trip and locked by reclosing.
- It has 1 input for external Trip/Reclose. This input is not opto - coupled.
- Mounting in Rail DIN 46277 (EN 50022) or panel 72x72 by mean accessory (M5ZZF1)
- Associated to a
WG WGS
/
Series external , toroidal current transformer.
- It must be asociated to a MCB motorized with or without a trip coil.
- It verifies connection with differential transformer
- Leakage detection and measurement is via calculating its true efective value (TRMS).
- Display settings values and instant residual current to its accociated units.
DESCRIPTION LED AND BUTTONS.
- Shows equipment status via a display and 2 LED.
- 5 button equipment setup and setting.
- 2 button equipment TEST and RESET.
-DELAY SETTING
-
SETUP
ROTATION
-SENSIVITY SETTING
-CONTACTS SETTING NO/NC
(LOCKED SIGNAL)
REC
-ENABLE/DISABLE
SELF-RECLOSING SYSTEM
INDICATION BY LED AND DISPLAY.
-
TRIP RELAY.
LED and display signals a change
of status by changing from green to red.l
Display event type messages or values.
BETWEN RECLOSURES.
-
The yellow LED is blinking. Red Display shows the
tripp cause fluctuating with partial reclosures No
LOCKED BY RECLOSURES
.
-
The yellow LED is fixed. The equipment arrives al
maximun number of reclosures established by the
self-reclosing sequence. Red display shows the cause.
-
No OF RECLOSURES.
By short press on
earth leakage, short ciruit-overload faults and total number. The partial number are floating pages
In these pages it can configure the self-reclosing sequence by press
RECLOSING THE EQUIPMENT.
- BY
TRIP LOCKED BY RECLOSURES
/
1. Automathic (earth leakage, short ciruit-overload faults or manual).
2. Manual reclose by pushing button
3. External reclose sytem by remote or communications signal. When it forces a trip by remote
signal, only it can reclose by another remote signal.
4. Manual reclose circuit breaker associated.
In the case 2 and 3 the all partial counters of reclosures returns to a zero.
The relay only self-recloses before a trip by earth leakage, short-circuit/overload current fault. The Test (red button) only
verifies the relay trips the protection. It recloses only by manual pressing RESET button.
RELAY PARAMETERS SETTING
-
SETTING TRIP DELAY
, .
t
The
PROG
d
pressing the
t
button. The lowest value indicates the current set value and the highest is the
d
values to be configured which are displayed by pressing
displayed by showing the message
SAVE.
-
SENSITIVITY SETTING
,
I
.
The same operation as above setting is carried out by pressing
d
- SIGNALLING CONTACTS RELAY STATE, std/+
7-8-9 that indicates the situation of locked by reclosures of the device . In (Std) 8-7 NA / 8-9 NC
and (+) 8-7 NC / 8-9 NA and appears the
- SELF-RECLOSING SYSTEM, REC
. In reclosure partial numbers by press
configure the self-reclosing sequence referred at the page which it's showing us. By default is
configured nº10 by earth leakage protection and nº5 by short-circuit/overload protection.
RECLOSE SEQUENCES BY EARTH LEAKAGE CURRENT FAULT
SREC
No RECLOSURES
TIME SEQUENCES
0
1
6
2
30
3
8
4
6
5
6
MAG
6
7
7
10
MAG
8
10
MAG
9
MAG
8
10
10
MAG
11
7
MAG
12
MAG
31
13
6
14
...
...
WARNING: The reclosing sequences marked by
without trip coil. I >63 A.
N
RGU-10C MT Electronic earth leakage protection relay with self-reclosing system
Type
Sensivity (A)
0,03-0,1-0,3-0,5-1-3
by direct adjustment
RGU - 10C MT
5-10-30 by SETUP
WG/WGS
by means inductive test.
PARAMETERS BY
DIRECT ADJUSTMENT
Tripping cause
Test
Remote signal trip/reclose
Earth leakage fault
Short circuit / Overload fault
Communications
Others MESSAGES by display
Enter setting values
SAVE
Exits setting mode
EXIT
Value reading off scale
OVR
Poor toroidal conection
ERRt
PROG
the display shows the number of reclosures by
REC
button.
REC
RESET
¡ IMPORTANT !
( , y std/+ )
t I
d
d
message and two values appear on the screen after
.
The selected value to be saved is
. Select the default position of the relay contacts
symbol in display.
+
RESET TIME
DISABLED
8, 16, 30, 59, 115 and 224 s
15 minutes
20, 40 s and 5 min. to the end
15 minutes
30 s, 1, 2, 3, 4, 5, 6 and 7 min
15 minutes
10, 20, 30, 60, 130 and 600 s
15 minutes
2, 4 and 8 min. to the end
15 minutes
30 s, 1, 2, 3, 4, 8 and 16 min.
30 minutes
1 min.
30 minutes
90 s
30 minutes
2, 4 and 6 minutes to the rest
15 minutes
3 minutes
2, 4, 8, 16, 32, 32 and 32 minutes
15 minutes
2, 4 and 6
minutes to the rest
15 minutes
8 s
15 minutes
...
is recommended for motorized circuit breakers with or
MAG
Tripping delay (s)
INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
by direct adjustment
3-5-10 by SETUP
RECLOSE SEQUENCE BY SHORTCIRCUIT/OVERLOAD FAULT
in LCD.
REC
SREC No RECLOSURES
MT
GREEN LED: ON
RED LED: TRIPPED BY FAULT
YELLOW LED: Locked by reclosures (fix)
RESET button: It reinitiates the operation of the equipment by any event
REC
TEST button: It makes a forced firing to verify the protection.
SCREENS / SETUP
REC
-
COM
-
FREQ
Message display
-
LIM
-
SEC. T
TESt
-
TRIP, (
EXT
-
RST.C
DIF / valor
MAG
SETUP SETTINGS
REM
A long press in
mode by pressing buttons
setting values to modify . With
validated, the message
mode. In case of keypad inactive, it exits setting mode and the message
EXIT
In
trip coil. The value
In
default 5-6 is normally open (St )
Enabled.
TECHNICAL FEATURES
- Tipo
- Reclosing type: Authomatic, RESET button or by cutting power supply.
- Rated power supply voltage
-
Operating temperature
-
Connections
Permissible cable section:
Recommended tightening torque: 0.5-0.6 Nm
Length of cable to strip:
-
Switch Output contact features
Rated current/Maximum instant current
Rated voltage/Maximum switching voltage
Rated load in
I
. .
Contacts protected by varistor
d
- Varistor Features
Maximun Voltage: 275 Va.c.
REC
button we
-Characteristics input remote Trip/Reclose 1-2
Input not using optocoupler
30 minutes
Communications
Available
RS-485
For instance, RGU-10C MT supplied by 110 V a.c.
TIME SEQUENCE
0
DISABLED
1
2
1 minute
2
2
1 minute
3
2
90 s
4
2
90 s
5
2
3 minutes
6
...
...
7
...
...
8
...
...
R
Betwen reclosures (blinking)
that tripps it.evento. It indicates the equipment version.
Default values in SETUP
, PER( ) / BD(
) / PAR( ), communications.
1
9.6
0
, (
50
) frecuency (Hz)
,(
1s, 3A
), range of values (Id / td)
, (
NO
),contacts 5-6 [
NA/NC]
MA
), breaking element
(without trip coil)
, (
NO
), initiates the partials counters.
PROG
activates the
PROG
and
PROG
SAVE
is shown by display and exits setting
is shown by display wihtout changes.
TRIP
(Circuit Breaker), The value
is used when CB needs one.
SEC.T
it defines the working mode of outputs contacts relay 5-6. By
Relay type: Electronic class A. High frequency current filtering.
: 230 o 110 Va.c. (+/- 20%) 50/60 Hz, 6 VA
: -10ºC / 50ºC
:
0,127 - 2,082 mm
7 mm
13-14-15, 7-8-9 and 5-6
AC: 2,500 V·A
P 2 X X X X 0 0 X
Código
Código interno
Code
Internal code
0
230 V a.c.
Tensión de
alimentación
110 V a.c.
1
P24652001
RESET TIME
30 minutes
60 minutes
30 minutes
60 minutes
30 minutes
...
...
...
Pulsador
PROG
1 ..
PERIPHERICS
.. 99
2.4
4.8
9.6
19.2
COM
BAUDS
38.4
57.6
115.0
0
EN
PARITY
OD
50 Hz
FREQ
60 Hz
10 s, 30 A
LIM
1 s, 3 A
St
SEC.T
PsI
MA
TRIP
Mb
NO
RST.C
YES
SETUP
settings. In this operating
it shows the submenus and the
these
new setting values are
is used when the CB don't need a
2
: 6/10 A a.c.
: 250/230 V a.c.
M98205901-03-09B
Need help?