Carrier 48LC Series Service And Maintenance Instructions page 18

Nominal 3 to 5 tons single package rooftop gas heating/electric cooling unit with puron (r-410a) refrigerant
Table of Contents

Advertisement

FIOP Smoke Detector Wiring and Response
GRA
GRA
BRN
CCHR
460/575V ONLY
1
1
BRN
2
2
WHT
DDC
T'STAT
3
3
GRN
4
4
PNK
All units: FIOP smoke detector is configured to
automatically shut down all unit operations when smoke
condition is detected. See Fig. 26, Smoke Detector
Wiring.
Highlight A: JMP 3 is factory- - cut, transferring unit
control to smoke detector.
Highlight B: Smoke detector NC contact set will open on
smoke
alarm
condition,
conductor.
Highlight C: 24- - v power signal via ORN lead is removed
at Smoke Detector input on CTB; all unit operations cease
immediately.
RTU Open Controls: Unit operating functions (fan,
cooling and heating) are terminated as described above. In
addition:
Highlight D: On smoke alarm condition, the smoke
detector NO Alarm contact will close, supplying 24- - v
power to GRA conductor.
Highlight E: WHT lead at Smoke Alarm input on CTB
provides 24- - v signal to FIOP DDC control.
RTU Open: The 24- - v signal is conveyed to RTU- - Open's
J1- - 10 input terminal. This signal initiates the FSD
sequence by the RTU Open control. FSD status is reported
to connected BAS network.
FIOP/
ACCESSORY
RETURN
SMOKE
SENSOR
SUPPLY
SMOKE
SENSOR
CCHTS
BLK
RED
BLK
X
C
G
W2
Fig. 26 - - Typical Smoke Detector System Wiring
de- - energizing
the
ORN
PL19-
1
POWER
10
BRN
BRN
24 VAC
2
9
RED
RED
RJ-45
4
16
ORN
ORN
NC
3
6
BLU
BLU
RJ-45
NO
5
17
WHT
WHT
6
14
YEL
YEL
24V
7
TROUBLE
3
PNK
PNK
NC
RED
8
GRA
5
GRA
ALARM
9
GRN
4
GRA
NO
SMOKE CONTROL
MODULE
FIOP/ACCESSORY
BRN
FIOP/ACCY
PNK
CONT
BRN
RED
RED
ORN
RED
24V
PMR
RED
BRN
COM
BRN
JMP2
JMP4
JMP3
CLO1/
COMP1
1
1
2
2
BRN
3
3
BRN
4
4
5
5
VIO
6
Using Remote Logic: Five conductors are provided for
field use (see Highlight F) for additional annunciation
functions.
Additional Application Data — Refer to Catalog No.
HKRNKA- - 1XA for discussions on additional control
features of these smoke detectors including multiple unit
coordination. See Fig. 26.
Sensor and Controller Tests
Sensor Alarm Test
The sensor alarm test checks a sensor's ability to signal an
alarm state. This test requires that you use a field provided
SD- - MAG test magnet.
CAUTION
!
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system,
notify
the
performing the test.
18
B
D
C
FROM POWER SCHEMATIC
TRAN
CB
24V
3.2 AMPS
GRN/YEL
BRN
BRN
5
CONTROL BD
24V
BRN
TRAN
BRN
RED
BRN
LCTB-C
COFS(FIOP)
BRN
COFS
F
YEL
RED GRA
BLU
WHT
PNK
BRN
GRA
RED
BRN
FOR FIELD USE
E
UNIT
SHUTDOWN
A
BRN
C
3
TDR BD
BLU
BLU
BLU
COFS (FIOP)
FPT
BRN
3
BLK
BLK
BLU
C
CLO1 TERM BD
48HC500010
C
proper
authorities
before
C14040