Zennio Securel ZIO-SEC User Manual

Zennio Securel ZIO-SEC User Manual

Access controller-encrypted relay

Advertisement

Quick Links

Securel
Access Controller – Encrypted Relay
ZIO-SEC
dsñkmfroi
Application Program Version: 1.1
User manual edition: [1.1]_a
www.zennio.com

Advertisement

Table of Contents
loading

Summary of Contents for Zennio Securel ZIO-SEC

  • Page 1 Securel Access Controller – Encrypted Relay ZIO-SEC dsñkmfroi Application Program Version: 1.1 User manual edition: [1.1]_a www.zennio.com...
  • Page 2: Table Of Contents

    4.1 Default status ........................9 4.2 Status after programming ....................9 4.3 Status after bus failure ..................... 9 4.4 Status after power failure ....................9 Configuration ........................10 5.1 General ........................... 10 ANEXO I. Communication Objects ....................12 http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 3: Introduction

    Securel 1 INTRODUCTION 1.1 SECUREL Securel from Zennio is a KNX actuator presented as a secure system for closing and opening doors of access-controlled rooms. It is located inside the room and it uses encrypted information to communicate with the access control device, known as IWAC.
  • Page 4: Access Control System

    IWAC and the notification of certain events. NFC card: passive element for accessing to certain rooms. As indicated before, for security reasons, the communication between IWAC and Securel is encrypted. Both IWAC and Securel are connected to the KNX bus. http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 5: Installation

    (1) and the terminal of the electric strike output as neutral (2). Moreover, the relay also will power IWAC with 24VDC through its remaining terminals (1) and (3). Finally, the Securel communicates with IWAC through the Tx/Rx transmit and receive terminal (4). Figure 3. Securel. Terminals. http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 6 To get detailed information about the technical features of this device, as well as on the installation and security procedures, please refer to the corresponding Datasheet, bundled with the original package of the device and also available at www.zennio.com. http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 7: Pairing With Iwac

    Whenever Securel is not paired, it will try to get paired by keeping the pairing mode active. While the device is in pairing mode no action can be performed in the output. For more information of the LED status during pairing, see section 3. http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 8: Led Notification

    In short, the different states that are notified are: Programming mode: Red LED Pairing mode (Securel not paired): Blue blinking. Relay Status (Securel paired):  Open (door closed): Green LED off.  Closed (door opened): Green LED http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 9: Securel Status

    When a power failure occurs, the electric strike is no longer powered; therefore it remains closed. When recovering from the power failure, Securel returns to idle state and therefore, the lock will be closed. On the other hand, after power failure, Securel keeps the previous pairing with the IWAC. http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 10: Configuration

    Heartbeat (Periodical Alive Notification): incorporates a one-bit object to the project (“[Heartbeat] Object to Send ‘1’”) that will be sent periodically with a value of “1” to notify that the device is still working (still alive). Figure 6. Heartbeat (Periodical Alive Notification). http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 11 255 seconds, to prevent bus overload. The following sendings match the period set. Note Take into account that Securel must be paired with the corresponding access control device (IWAC) to work properly (for further information, see section 2). http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 12: Anexo I. Communication Objects

    KNX standard or the application programme itself. Number Size Flags Data type (DPT) Functional Range Name Function 1 Bit C T - - - DPT_Trigger [Heartbeat] Object to Send '1' Sending of '1' Periodically http://www.zennio.com Technical Support: http://support.zennio.com...
  • Page 13 Join and send us your inquiries about Zennio devices: http://support.zennio.com Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo (Spain). Tel. +34 925 232 002 www.zennio.com info@zennio.com...

This manual is also suitable for:

SecurelZio-sec