Table 14. Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence, operate value
Harmonic frequency dependence (20%
content)
Type tests according to standards
Table 15. Electromagnetic compatibility
Test
1 MHz burst disturbance
100 kHz slow damped oscillatory wave
immunity test
Ring wave immunity test, 100 kHz
Surge withstand capability test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance
Surge immunity test
Power frequency immunity test
Conducted common mode immunity test
Power frequency magnetic field test
Damped oscillatory magnetic field test
Radiated electromagnetic field disturbance
Radiated electromagnetic field disturbance
Conducted electromagnetic field disturbance
Radiated emission
Conducted emission
Within nominal range
f
± 2.5 Hz for 50 Hz
r
f
± 3.0 Hz for 60 Hz
r
2nd, 3rd and 5th harmonic of f
Type test values
2.5 kV
2.5 kV
2-4 kV
2.5 kV, oscillatory
4.0 kV, fast transient
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
1-2 kV, 1.2/50 ms
high energy
150-300 V, 50 Hz
15 Hz-150 kHz
1000 A/m, 3 s
100 A/m, cont.
100 A/m
20 V/m, 80-1000 MHz
1.4-2.7 GHz
35 V/m
26-1000 MHz
10 V, 0.15-80 MHz
30-1000 MHz
0.15-30 MHz
1MRK 511 266-BEN -
Influence
± 1.0% / Hz
± 1.0%
r
Reference standards
IEC 60255-22-1
IEC 61000-4-18, Class III
IEC 61000-4-12, Class IV
IEEE/ANSI C37.90.1
IEC 60255-22-2, Class IV
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.1
IEC 60255-22-4, Class A
IEC 60255-22-5
IEC 60255-22-7, Class A
IEC 61000-4-16, Class IV
IEC 61000-4-8, Class V
IEC 61000-4-10, Class V
IEC 60255-22-3
IEEE/ANSI C37.90.2
IEC 60255-22-6
IEC 60255-25
IEC 60255-25