ABB Relion 670 Series Product Manual page 30

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Phasor measurement unit RES670
Pre-configured
Product version: 1.2
Table 11. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
Max system voltage
Test voltage across open contact, 1 min
Current carrying capacity
Continuous
1 s
Making capacity at inductive load with L/R>10 ms
0.2 s
1.0 s
Breaking capacity for AC, cos j>0.4
Breaking capacity for DC with L/R < 40 ms
Influencing factors
Table 12. Temperature and humidity influence
Parameter
Ambient temperature,
operate value
Relative humidity
Operative range
Storage temperature
Table 13. Auxiliary DC supply voltage influence on functionality during operation
Dependence on
Ripple, in DC auxiliary voltage
Operative range
Auxiliary voltage dependence, operate
value
Interrupted auxiliary DC voltage
Interruption interval
0–50 ms
0–∞ s
Restart time
30
Reference value
+20 °C
10%-90%
0%-95%
-40 °C to +70 °C
Reference value
max. 2%
Full wave rectified
Trip and Signal relays
24
250 V AC, DC
1000 V rms
8 A
10 A
30 A
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Nominal range
-10 °C to +55 °C
10%-90%
-
Within nominal
Influence
range
15% of EL
0.01% /%
± 20% of EL
0.01% /%
24-60 V DC ± 20%
90-250 V DC ± 20%
No restart
Correct behaviour at power
down
<180 s
1MRK 511 266-BEN -
Influence
0.02% /°C
-
-
ABB