ABB ADVAC 03 Installation & Maintenance Instructions Manual page 20

Medium voltage vacuum power circuit breakers and auxiliary
Table of Contents

Advertisement

ABB IB 6.2.15.7-1C
A. Current energizes 52TC
To verify the integrity of the primary insulation, perform the following low-frequency withstand voltage test:
1. Close the breaker (no control power supplied to breaker)
a. Connect the high potential lead to one pole
b. Ground the remaining poles and breaker frame
2. Start machine with output potential at 0 (zero) VAC.
3. Increase the potential to the required voltage (see Table 2)
4. Hold for one minute
5. Decrease potential to 0 (zero) VAC and turn off machine
6. Repeat for the remaining poles
A successful withstand indicates satisfactory insulation strength
of the primary circuit.
To verify the integrity of the vacuum interrupters perform the following low-frequency withstand voltage test:
1. Open the breaker (no control power supplied to breaker)
a. Connect the high potential lead to one terminal
b. Ground the remaining 5 terminals and breaker frame
2. Start machine with output potential at 0 (zero) VAC
3. Increase the potential to the required voltage (see Table 2)
4. Hold for one minute
5. Decrease potential to 0 (zero) and turn off machine
6. Repeat for the remaining 5 terminals
A successful withstand indicates satisfactory vacuum integrity.
Replace pole assemblies that fail to withstand the voltage across the open contacts, ( if flashover occurs).
Testing should be done with an AC source only. DC testing is not considered a valid test for vacuum integrity. If
DC is the only available option, the peak DC voltage should not exceed the corresponding AC RMS test voltage.
Additionally, a failure during DC testing should only be considered preliminary. Additional AC testing should be
completed before replacement of the pole is considered to be warranted. Testing with meggers or other similar
devices is not considered valid under any circumstances.
MAINTENANCE
CAUTION
Applying abnormally high voltage across a pair of open contacts in
vacuum may produce X-radiation. The radiation may increase with
the increase in voltage and/or decrease in contact spacing. It is
recommended that all operating personnel stand at least one meter
away and in front of the circuit breaker during testing.
Rated Max
Dielectric Test
Voltage
Value, 1 Minute
Dry AC rms
4.76kV
15kV
8.25kV
27kV
15kV
27kV
Table 2: Primary Low-Frequency Withstand Test
Voltages
20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Advac

Table of Contents