1. Connect the water supply to the fill valve and open the valve.
2. Make sure the automatic air purge valve is open (at least 2 turns).
3. Fill with water until the manometer indicates a pressure of
approximately 2.0 bar. Remove air in the circuit as much as
possible using the air purge valves. Air present in the water circuit
might cause malfunctioning of the backup heater.
Do not fasten plastic cover
on the air purge valve at the
topside of the unit when the
system is running. Open air
purge valve, turn
anticlockwise at least 2 full
turns to release air from the
system.
I
A
,I QRWKLQJ LV GLVSOD\HG RQ WKH XVHU LQWHUIDFH LW LV QHFHVVDU\ WR
check for any of the following abnormalities before diagnosing
possible error codes.
'LVFRQQHFWLRQ RU ZLULQJ HUURU EHWZHHQ SRZHU VXSSO\ DQG XQLW
and between unit and user interface).
7KH IXVH RQ WKH 3&% PD\ KDYH EORZQ
I
A
10
HP
11
LP
12
1
1
Compressor
2
4-Way Valve
3
Accumulatior
4
Air Side Heat Exchanger
5
Electronic Expansion Valve
6
Storage Tank
7
Strainer
8
Water Side Heat Exchanger
(Plate Heat Exchange)
17
FAILURE DIAGNOSIS AT THE MOMENT OF FIRST INSTALLATION
15
8
16
2
3
9
Differential Pressure Switch
10 High Pressure Switch
11 Low Pressure Switch
12 Discharge Gas thermistor
13 thermistor For Outdoor Temperature
14 Thermistor For Evaporation In Heating
(Thermistor For Condenser In Cooling)
15 Thermistor For Plate Heat Exchange 1
16 Thermistor For Plate Heat Exchange 2
During filling, it might not be possible to remove all air in the
system. Remaining air will be removed through the automatic
air purge valves during the first operating hours of the system.
Topping up the water afterwards might be required.
7KH ZDWHU SUHVVXUH LQGLFDWHG RQ WKH PDQRPHWHU ZLOO YDU\
depending on the water temperature (higher pressure at
higher water temperature).
However, at all times water pressure should remain
above 0.3 bar to avoid air entering the circuit.
7KH XQLW PLJKW GUDLQRII WRR PXFK ZDWHU WKURXJK WKH
pressure relief valve.
:DWHU TXDOLW\ PXVW EH DFFRUGLQJ WR 6DIH 'ULQNLQJ ZDWHU
$FW
,I WKH XVHU LQWHUIDFH VKRZV
a possibility that there is air in the system, or the water level in the
system is less than the required minimum.
,I WKH HUURU FRGH
wiring between the user interface and unit.
20
19
17
9
18
6
7
13
4
14
FILLING WITH WATER
127(
DV DQ HUURU FRGH WKHUH LV
is displayed on the user interface, check the
REFRIGERANT CIRCUIT
22
23
21
24
A
5
7
Cooling
Heating
17 Thermistor For Water Outlet
18 Thermistor For Water Inlet
19 Automatic Discharge Valve
20 Expansion Tank
21 Circulating Pump
22 Pressure Gauge
23 Safety Valve
24 Auto-watet replenishing