Ultra Heat GMV Multi VRF_Heat Recovery Serial
can be seen in Master Unit Setup S7 of Technical service manual (Set master unit S7 as "00"; Set slave
unit S7 as "10").
Step 4: Connect power for all indoor units. Make sure all IDUs are power on. Then all outdoor
modules will display "A0".
Step 5: Find the module with "00" of S7 which is the master module. The main board shows:
Debugging code
Code
A0
Hold SW4 button on the master module for at least 6s to enable debugging. Then the main board
shows:
Debugging code
Code
A0
Press SW4 confirmation button on the master unit to confirm it. Unit will start debugging.
Step 6: Wait. Unit will then start progress 01.
If no error is detected, system will display as below and then start next progress.
——
progress
01_Set up master unit
If unit have some errors, progress 01 will show the following errors:
——
Debugging Code
Progress
Code
CC
01_Set up
CF
master unit
CJ
According to the above errors, reset the master unit (Set master unit S7 as "00"; Set slave unit S7 as
"10"), then start debugging again.
Step 7: Progress 02 is allocating addresses. If allocating addresses is done, then main board
shows:
——
Progress
LED1
Display status
code
Light
LED1
Display status
code
Blink
Debugging code
LED1
Code
Display status
db
Light
Progress Code
LED1
LED2
Display
Code
status
Light
Light
Light
Debugging code
LED1
Code
Display status
Progress code
LED2
Display status
Progress code
LED2
Display status
Progress code
LED2
code
Display status
01
Status Code
LED3
Display
Display
Code
status
status
Progress code
LED2
Code
Display status
49
Status code
LED3
Code
Display status
0
Light
Status code
LED3
Code
Display status
Status code
Code
Light
oC
Meaning
System doesn't have master unit.
Reset master unit.
More than 2 master units are set.
Reset master unit.
Address DIP switch code of system is
shocking.
Status code
Code
LED3
Display status
Light
LED3
Display status