Capacity Code - Gree ULTRA heating GMV5 Multi VRF Series Service Manual

Table of Contents

Advertisement

Ultra Heating GMV5 Multi VRF
for North America

5.2 Capacity Code

Instruction of capacity code:
GMV-36WL/B-(U) and GMV-48WL/B-(U) are identical in components, systems and structure, etc.
5.3 Capacity Correction Formula5.1 Correction factor of indoor and outdoor temperature
5.3.1 Rated capacity of outdoor unit
Rated cooling capacity
Rated heating capacity
5.3.2 Correction factor of indoor and outdoor temperature
(1) Correction factor of cooling capacity
(2) Correction factor of heating capacity
5.3.3 Correction factor of pipe length and height difference
(1) Symbol description:
Hp: Height difference in case indoor unit is below outdoor unit(m/feet);
Hm: Height difference in case indoor unit is above outdoor unit (m/feet);
L: Length of one-way equivalent pipe.
Below table shows the capacity variance ratio for 100% full load in standard working condition (thermostat setting is 16
10
PRODUCT
Model
kW(Btu/h)
kW(Btu/h)
0.95
48
(118)
45
(113)
40 (104)
35
(95)
30
(86)
25
(77)
20
(68)
16
(61)
14
(57) (61) (64) (68) (72) (75) (79)
         
-25
-20
(-13
(-4)
GMV-36WL/B-T(U)
10.5(36000)
13.2(45000)
1.00
1.00
1.00
1.00 1.05
16
18
20
22
24
0.95
1.0
1.0
1.0
1.00
GMV-48WL/B-T(U)
14.1(48000)
15.8(54000)
26
o
o
C(61
F) for

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ULTRA heating GMV5 Multi VRF Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Ultra heating gmv-36wl/b-tUltra heating gmv-36wl/b-tuUltra heating gmv-48wl/b-tUltra heating gmv-48wl/b-tuUltra heating gmvnd07pls/a-tUltra heating gmvnd07pls/a-tu ... Show all

Table of Contents