FIGURE 6A. INSTALLATION OF XP6-R MODULE IN A REAR CHASSIS
POSITION, METHOD TWO:
1
Step 1: Install two long standoffs in the lower mounting holes using two 4-40
nuts as shown.
FIGURE 6B.
3
2
Step 2: Insert the bottom of the XP6-R module down into a rear slot on the
chassis.
Step 3: Carefully swing the upper edge of the board back towards the back of
the chassis until it touches the two standoffs on the board.
Step 4:
Align two 4-40 screws with the two standoffs on the chassis and
tighten.
Step 5: Address and wire the modules according to the instructions in this
manual.
FIGURE 6C. INSTALLATION OF XP6-R MODULE IN FRONT CHASSIS
POSITION:
2
1
Step 1: Insert the bottom edge of the XP6-R module down into a front slot of
the chassis.
Step 2: Carefully swing the upper edge of the board towards the back of the
chassis until it touches the 11/4˝ (31.75mm) standoffs installed on
the rear module.
N500-78-00
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instructions in this
manual.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Make electrical connections by stripping approximately ¼˝ (6.35mm) of
insulation from the end of the wire sliding the bare end of the wire under
the clamping plate, and tightening the clamping plate screw.
3.
Set the address on the modules per the job drawing. Use the rotary code
switches to set the address of the first module (between 01 and 154). The
remaining modules are automatically assigned to the next five higher
addresses. For example, if the base address switch is set to 28, the next
five modules will be addressed to 29, 30, 31, 32, and 33. DO NOT set
the lowest address above 154, as the other modules will be assigned to
nonexistent addresses.
C0225-01
NOTE: Some panels support extended addressing. In order to set the module
above address 99 on compatible systems, carefully remove the stop on the up-
per rotary switch. If the panel does not support extended addressing, do not
set the lowest addressabove 94.
4.
A shunt is provided to disable a maximum of three unused modules.
Modules are disabled from the highest address and work downward. If
two modules are disabled, the lowest four addresses will be functional,
while the highest two will be disabled. For example, if the shunt for Ad-
4
dress Disable is placed on "two" and the base address switch is set to 28,
the modules will be assigned to 28, 29, 30 and 31.
NOTE: Power must not be applied to the unit when changing functionality of
the shunts.
NOTE: The XP6-R must have power cycled for shunt changes to take effect.
NOTE: All references to power limited represent "Power Limited (Class 2)".
C0249-01
3
C0226-01
3
I56-1804-012