Specification
Rated input voltage
Rated input frequency
Maximum input current per
line cord
Maximum input power per
line cord

Three-phase power (International)

Specification
Power cords (2)
Output
Input requirements
Rated input voltage
Rated input frequency
Maximum input current per
line cord
Maximum input power per
line cord
*Rated 220 VAC to 240 VAC line-to-neutral. The enclosure does not operate from higher line-to-line voltage with the
WYE wall plug configuration. Input AC modules are configured to provide 220 VAC to 240 VAC to the power supplies
in this system.

Hot-plug power supply calculations

For hot-plug power supply specifications and calculators to determine electrical and heat loading for the
server, see the HP Power Advisor website (http://www.hp.com/go/hppoweradvisor).
HP 2450W Platinum Hot Plug
Redundant Power Supply
200 VAC to 208 VAC line to line
3-phase delta
50 Hz to 60 Hz
22.9 A at 200 VAC
22 A at 208 VAC
7920 VA
HP 2450W Platinum Hot Plug
Redundant Power Supply
IEC-309 200/380-V to 240/415-V,
5-pin, 16-A
3.05 m (10 ft)
2450 W
380 VAC to 415 VAC line-to-line*
220 VAC to 240 VAC line-to-neutral
3-phase WYE
50 Hz to 60 Hz
12.2 A at 220/380 VAC
11.2 A at 240/415 VAC
8064 VA
HP 2650W Platinum Hot Plug
Redundant Power Supply
200 VAC to 208 VAC line to line
3-phase delta
50 Hz to 60 Hz
25 A at 200 VAC
24 A at 208 VAC
8640 VA
HP 2650W Platinum Hot Plug
Redundant Power Supply
IEC-309 200/380-V to 240/415-V,
5-pin, 16-A
3.05 m (10 ft)
2650 W
380 VAC to 415 VAC line-to-line*
220 VAC to 240 VAC line-to-neutral
3-phase WYE
50 Hz to 60 Hz
13.1 A at 220/380 VAC
12 A at 240/415 VAC
8646 VA
Specifications 42