Power specifications
The power requirements for the HP Apollo a6000 5U Chassis are met by the following components:
•
HP 2450W Platinum Hot Plug Redundant Power Supply
•
HP 2650W Platinum Hot Plug Redundant Power Supply
•
HP Apollo 6000 Power Shelf
•
AC Input Module
•
Power Management Module
DC power
Specification
Output
Minimum (V)
Nom (V)
Maximum (V)
% Reg
Single-phase power
Specification
Power cord
Output
Input requirements
Rated input voltage
Rated input frequency
Rated input current per
power supply (maximum)
Rated input power per
power supply (maximum)
Three-phase power (North America/Japan)
Specification
Power cord
Output
Input requirements
Value
12V from power supplies to
system chassis
+11.907
+12.25
+12.593
+2.8%/-2.8%
HP 2450W Platinum Hot Plug
Redundant Power Supply
IEC-320 C19-C20
2 m (6.5 ft)
2450 W per power supply
200 VAC to 240 VAC
50 Hz to 60 Hz
13.2 A at 200 VAC
12.7 A at 208 VAC
12.2 A at 220 VAC
2640 VA
HP 2450W Platinum Hot Plug
Redundant Power Supply
NEMA L15-30p
3.05 m (10 ft)
2450 W per phase
HP 2650W Platinum Hot Plug
Redundant Power Supply
IEC-320 C19-C20
2 m (6.5 ft)
2650 W per power supply
200 VAC to 240 VAC
50 Hz to 60 Hz
14.4 A at 200 VAC
13.8 A at 208 VAC
13.1 A at 220 VAC
2880 VA
HP 2650W Platinum Hot Plug
Redundant Power Supply
NEMA L15-30p
3.05 m (10 ft)
2650 W per phase
Specifications 41