ABB ACS880-07 Series Hardware Manual page 17

Industrial drives
Hide thumbs Also See for ACS880-07 Series:
Table of Contents

Advertisement

• Before you adjust the drive operation limits, make sure that the motor and all driven
equipment can operate throughout the set operation limits.
• Before you activate the automatic fault reset or automatic restart functions of the drive
control program, make sure that no dangerous situations can occur. These functions
reset the drive automatically and continue operation after a fault or supply break. If these
functions are activated, the installation must be clearly marked as defined in
IEC/EN 61800-5-1, subclause 6.5.3, for example, "THIS MACHINE STARTS
AUTOMATICALLY".
• The maximum drive power cycles is five times in ten minutes. Power cycling the drive
too often can damage the charging circuit of the DC capacitors.
• If you have connected safety circuits to the drive (for example, Safe torque off or
emergency stop), validate them at start-up. See separate instructions for the safety
circuits.
• Beware of hot air exiting from the air outlets.
• Do not cover the air inlet or outlet when the drive is running.
Note:
• If you select an external source for the start command and it is on, the drive will start
immediately after fault reset unless you configure the drive for pulse start. See the firmware
manual.
• If the drive is in remote control mode, you cannot stop or start the drive with the control
panel.
• Only authorized persons are allowed to repair a malfunctioning drive.
Safety instructions 17