Setting groups
Figure 3.21
Setting Groups menu displays all the information related to group changing.
Active setting group displays the current active setting group 1...8.
It is possible to activate desired setting group by setting Force SG. While doing this Force SG change has to be enabled.
In Used setting groups menus it is possible to activate setting groups between 1 and 1...8 (default only 1 group is active).
Select local control for different setting groups from SG Local Select. Digital inputs, Logical inputs or outputs, stage starting-
tripping- or blocking, RTDs and object status information can be used.
Event masking for setting groups (masks are off as default). Only masked events appear to event list. Events cannot be cleared.
Setting group 1 has the highest and group 8 the lowest priority. Setting groups can be controlled with steady signal or pulses.
Figure 3.22
Group changing with pulse control only or with pulses and static signal.