Deif MVR-200 Series Operator's Manual page 19

Medium voltage relay
Table of Contents

Advertisement

Figure 3.10
Stage information is divided into two sections.
Starting and tripping signals of protection stages are connected to physical outputs in Direct Output Control menu. It is possible to
connect to output relay or to start- trip- or user configurable LED. In case when stage is internally blocked (DI or other signal) it is
possible to configure an output to indicate that stage is blocked. Connection to outputs can be either latched |x| or non-latched x.
Stage blocking is done in Blocking Input Control menu. Blocking can be done by using digital inputs, logical inputs or outputs, stage
start- trip- or blocked information or by using object status information.
OPERATOR'S MANUAL 4189341220A UK
Page 19 of 51