Modbus Rtu Communication; Rs485 Communication Interface; Communication Parameters; Modbus Holding Registers - Evikon PluraSens E2658-ETO User Manual

Ethylene oxide detector-transmitter
Table of Contents

Advertisement

E2658-ETO 
Modbus RTU Communication 
RS485 communication interface 
Databits: 8   
Parity: none / odd / even   
Stop bits: 1 or 2   
Protocol: Modbus RTU 
 
Communication parameters 
Parameter 
Supported baud rates  1200, 2400, 4800, 9600, 19200, 38400, 57600 
Data bits 
Parity 
Stop bits 
Protocol 
Modbus functions 
Error codes 
Modbus holding registers 
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format. 
Modbus holding register numbers MHR are shown in the decimal 1-based format and may
 
 
be addressed either from 00001 or 40001 base. 
Addr 
Reg / MHR  RW  Description 
0x0001 
1 / 40002  R 
0x0002 
2 / 40003  R 
0x0003 
3 / 40004  R 
0x0004 
4 / 40005  RW  Slave ID (net address) * 
0x0005 
5 / 40006  RW  Baud rate * 
Permitted values 
none / odd / even 
1, 2 
Modbus RTU 
03 - Read multiple registers 
06 - Write a single register 
01 – Illegal function 
02 – Illegal data address 
03 – Illegal data value 
04 – Slave device failure  
(details of last error 04 can be read from register 0x0008) 
 
 
Hardware version 
Software version 
Product serial number 
Supported Modbus functions: 
03 – Read multiple registers  
06 – Write a single register 
 
 
   
 
Supported values (dec) 
 
 
1...65535 
1...247 ** 
1200, 2400, 4800, 9600, 
19200, 38400, 57600 
16 
Rev 16.12.2020 
 
 
 
Default 
Default 
9600 
none 
 
 
 
9600 

Advertisement

Table of Contents
loading