8. SPECIAL INSTRUCTION FOR USE

- The equipment shall only be used in an area of not more than
pollution degree 2, as defined in IEC/EN 60664-1.
- The equipment shall be installed in an enclosure that provides
a degree of protection not less than IP 54 in accordance with
IEC/EN 60079-15.
- Transient protection shall be provided that is set at a level
not exceeding 140 % of the peak rated voltage value at the
supply terminals to the equipment.
- Install the HMI device according to the accompanying
installation instructions.
- Ground the HMI device according to the accompanying
installation instructions.
eView HD IP67 HMI products delivery configuration is
based on a loader. Use the services of the loader to install
applications on the device such as GF Designer HD runtime
or browsers.
GF Designer HD or higher is required. GF Designer HD is a
software tool that must be properly installed on a computer
running Microsoft Windows.
There are two options to transfer a GF Designer HD application
project to a HMI device:
17

9. GETTING STARTED

- Only qualified personnel may install the HMI device or
repair it.
- Care shall be taken not to allow layers of dust to form on the
graphic panel in a way that might cause the accumulation of
static charges. Keep the faceplate of the HMI device clean:
the equipment must be cleaned only with a soft cloth and
neutral soap product. Do not use solvents.
- This device should not be used for purposes and methods
other than indicated in this document and
documentation accompanying the product.
Ethernet
Connect the HMI device to the computer with
an Ethernet network. In GF Designer HD select
the command Run/Download to target. You may
have to ensure that the proper firewall policy has
been configured in the computer to allow GF
Designer HD to access the network.
USB
Create an Update Package using GF Designer
HD and copy it to a USB Flash drive (to transfer
via USB, use the dedicated accessory cable).
80588_eView HD IP67_02-2019_ENG