14.1 A shower pipe (e.g. HT pipe, d
to deflect the hot water to avoid scalding during the thermal disinfection process.
14.2 Turn the temperature selector (a) to the hot water stop.
14.3 Use the Allen key to push in the stop.
14.4 Turn the temperature selector (a) in an anti-clockwise direction up to the stop.
14.5 Trigger the fitting.
14.6 Measure the hot water temperature.
14.7 If the hot water temperature is > 70°C, the fitting should be flushed for at least 3
minutes. Trigger the fitting several times for this purpose.
The thermal disinfection process must be recorded (room, tapping point, date, time,
temperature, duration).
14.8 Turn the temperature selector (a) clockwise until it engages.
Caution!
The temperature selector (a) may not be turned beyond the stop in an anti-
clockwise direction.
14.9 Test the limit stop.
14.10 Trigger the fitting to drain the remaining hot water.
14.11 Measure the water temperature. The maximum water temperature may not exceed
40°C (see
Chapter
Once thermal disinfection has been completed, the scald protector does not need to
be reset.

15. Thermal disinfection -with solenoid valve cartridge-

Caution!
The directions in the Thermal Disinfection Planning Aid (01805618) must be
adhered to.
Required accessories
Bypass solenoid valve cartridge . . . . 2000100431
Connection cable for
Bypass solenoid valve cartridge. . 2000100432
Key switch . . . . . . . . . . . . . . . . . . . . . 2000102675
Power pack (12 W) . . . . . . . . . . . . . . 2000100375
Power pack (48 W) . . . . . . . . . . . . . . 2000100433
= 100 mm) should be placed under the shower head
i
16.).