SECTION 2.

Installation Instructions

2.1 General Information

Follow local regulations with respect to installation
of carbon monoxide (CO) detectors and
manufacturer's maintenance schedule of the heater.
Install the Copper Brute heaters in accordance
with the procedures in this manual (or the warranty
may be voided), local codes and ordinances. In the
absence of such codes, install the heaters in accordance
with the latest edition of the National Fuel Gas Code,
ANSI Z223.1. In Canada, the installation must be
in accordance with CAN1-B149.1 or .2 and local
codes. The authority having jurisdiction may require
the installation conform to the Standard for Controls
and Safety Devices for Automatically Fired Heaters,
ANSI/ASME CSD-1. Any changes to the heater, gas
controls, gas orifices, wiring or draft diverter may void
the warranty. If field conditions require a change to
any of the above, consult the factory.
All gas-fired products require correct installation
to assure safe operation. The requirements for heaters
include the following:
1.
Field assembly of drafthood or vent cap (see
Section 2.2).
2.
Appropriate site location (clearances) and
flooring.
3.
Sufficient combustion and ventilation air.
4.
Adequate venting of combustion products.
5.
Adequate water flow.
6.
Properly sized gas meter and piping.
7.
Proper electrical wiring.
This manual provides the information needed to
meet these requirements. Review all application and
installation procedures completely before continuing
the installation.

2.2 Field Assembly

The Copper Brute heater is shipped from the
factory with the top assembly in the low-profile
configuration for outdoor installations.
The Copper Brute heater is design certified
for indoor installation when equipped with a
special drafthood, which must be installed without
modification. The part number for the drafthood is on
the heater rating plate. Follow this procedure to make
the conversion:
WARNING
a.
Remove the top filler plate, stamped "HOT", by
slipping a fine-blade screwdriver into the slot at
the rear of the plate and gently prying it up (see
Figure 2).
b.
Remove the two screws attaching the adapter
plate to the top assembly and lift it out (see
Figure 3).
c.
Remove the vent cap or drafthood from its
package.
d.
Disengage the flue transition ring from the stack
extension and place it on top of the collector
assembly as shown in Figure 4.
Figure 2. Top filler plate.
Figure 4. Flue transition
ring.
Figure 6. Drafthood with
adapter plate
(indoor).
BRADFORD WHITE
Figure 3. Adapter plate.
Figure 5. Vent cap with
adapter plate
(outdoor).
Figure 7. Drafthood switch
receptacle.