Testing For Burner Ignition (For Standing Pilot); Heater Will Not Shut Off; On-Off Main Burner Cycling; Testing The Terminal Strip/External Controls - Bradford White Copper Brute B4 Installation, Operation & Maintenance Instructions Manual

Volume water heaters
Hide thumbs Also See for Copper Brute B4:
Table of Contents

Advertisement

Internet Version for Reference Only
Copper Brute B4 Volume Water Heaters
Thermocouple
Figure 42. Testing the pilot thermocouple.
1.
Check all wire connections, ignition cable, and
using a mirror, make sure there is a pilot flame.
2.
If everything appears all right, measure flame
sensing current by connecting a direct current
(DC) microamp meter between terminal No.
12 and the GND (BURNER) terminal on the
ignition control (see Figure 43).
NOTE: Separate the microamp meter leads from
each other and clear the heater chassis for most of their
length to properly perform this test.
3.
When the pilot lights, the microamp meter should
read 1.5 microamps or more with or without the
main burners firing. A smaller current could be
caused by poor pilot flame, the position of the
pilot electrode, or bad cable and connectors.
4.
If the pilot flame and sensor electrode are all
right, but there is no main burner ignition, clip
one lead from a volt meter between the yellow
wire terminal on the transformer and the brown
wire terminal on the gas valve.
5.
If the voltmeter reads between 20 to 28VAC,
but the main burners do not fire, replace the gas
valve (see Section 4.2).
5.2.15 Testing for Burner Ignition
If the pilot flame and pilot thermocouple
generator are all right, but there is no main burner
ignition:
1.
Clip one lead of a volt meter between the yellow
wire on the transformer and the brown wire
terminal on the gas valve.
2.
If the volt meter reads between 20 to 28VAC,
but the main burners do not fire, replace the gas
valve (see Section 4.2).
Thermocouple
Adapter
Gas Valve
Pilot
Millivolt
Meter
(for standing pilot)
Figure 43. Flame sensing current.

5.2.16 Heater Will Not Shut Off

1.
If the heater stays on with the brown wire on the
gas valve disconnected, replace the gas valve
(see Section 4.2).
WARNING
Never attempt to repair the gas valve. Such
attempts will void the warranty, and could lead to
dangerous results.
2.
Check electrical components for loose wires.
Disconnect one of the lead wires on the gas
valve. If the heater goes off, the wiring could be
at fault. Repair or replace as necessary.

5.2.17 On-Off Main Burner Cycling

The main burners cycling on and off can be
caused by:
1.
Poor wind conditions on an outdoor installation.
2.
Pilot components out of position.
3.
Low gas pressure causing an improper pilot
flame.
The pilot flame may appear to be all right until
the main burners come on, then the pilot flame shrinks.
An undersized gas supply line may cause this.
5.2.18 Testing the Terminal Strip/
External Controls
The terminal strip has been included so the
heater can be operated by various external controls not
provided by Bradford White. Determine whether or
not an external control is open by checking for voltage
at each terminal. If there is voltage at one terminal
and not the other, examine the external control. It may
require service or replacement.