Safely-limited speed with the encoder interface (option +q965)
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

limit during monitoring. The FSO module can activate the SSE function in internal fault
situations.
Index
Name
SSE.13
SSE function
SSE.14
SSE monitoring
method
SSE.15
SSE delay for STO
Example value
Description
Immediate STO or
Sets the type of the SSE function.
Emergency ramp
Immediate STO: The FSO module activates
the drive STO function immediately after the
SSE request.
Emergency ramp: The FSO module deceler-
ates the motor to zero speed, and then ac-
tivates the drive STO function. SAR0 para-
meters define the deceleration ramp. For
more information, see the FSO module
user's manual. Zero speed is defined by
parameter FSOGEN.51 Zero speed without
encoder or FSOGEN.52 Zero speed with
encoder.
For option +Q965, ABB sets this parameter
to value Immediate STO at the factory. Ad-
just the default value when necessary.
Ramp or Time
Sets the method used for the SSE emer-
gency ramp monitoring. This parameter is
relevant only if parameter SSE.13 SSE
function is set to Emergency ramp.
Ramp: SAR0 parameters define the emer-
gency ramp and monitoring limits (see SAR0
ramp settings).
Time: Parameter 200.102 SAR0 ramp time
to zero defines the emergency ramp and it
is monitored with parameter SSE.15 SSE
delay for STO.
For option +Q965, ABB sets this parameter
to value Ramp at the factory. Adjust the de-
fault value when necessary.
20000 ms
Sets the SSE monitoring time after which
the FSO module activates the drive STO
function after the SSE request.
This parameter is relevant only if parameter
SSE.13 SSE function is set to Emergency
ramp, time monitoring is used (SSE.14 SSE
monitoring method is set to Time) and the
motor speed does not follow the ramp.
Note: This delay must be considered when
the total response time for the safety func-
tion is defined.
Parameter settings 41