10. Insert the power cord retention tabs into the slots on the enclosure
until they snap into place.
11. Slide each snap clamp over the end of each power cord
overmold, and then squeeze each snap clamp closed.
Three-phase power configuration
For a three-phase power configuration, the AC power cables are
already attached to the enclosure. To cable the enclosure using a
three-phase AC configuration:
1.
Connect the AC power cables to the AC power source.
2.
Turn on the AC circuit breakers that power the power cables
installed in the enclosure.
The installation is complete.
Setting up the HP BladeSystem
Insight Display
To identify the enclosure, the rear enclosure UID light and the
background of the Insight Display are illuminated blue when the
enclosure is powered on initially. When the enclosure is powered up
for the first time, the Insight Display launches an installation wizard to
guide you through the configuration process. At the beginning of the
installation, the wizard automatically powers on the enclosure UID.
After the installation is complete, the wizard powers off the enclosure.
After configuring the enclosure, the Insight Display verifies that there
are no installation or configuration errors. If errors are present, the
Insight Display guides you through the process of correcting the errors.
To set up an enclosure with network connectivity to the Onboard
Administrator with KVM:
1.
On the Enclosure Settings screen, confirm the default settings.
o
Use the navigation arrows to navigate to a particular setting,
and then press OK.
o
Navigate to the ? box next to a setting, and then to get help,
press OK.
2.
Confirm the Power mode for the power supplies, which is
typically AC Redundant.
3.
If the facility must limit AC power to the enclosure below what the
power supplies can draw, set the Power Limit.
4.
To provide the highest power efficiency without affecting server
performance, enable Dynamic Power Savings.
5.
Record the OA1 and OA2 (if present) IP address. This
information is needed when deploying the management
software.
o
If the OA1 or OA2 IP address is 0.0.0.0., set the address.
Navigate to the address, and then press OK. Use the up and
down arrows to select Static IP address. Use the up and
down arrows on each field to set the IP, netmask, and
gateway one octet at a time. Press OK, and then press OK
again on Accept to confirm the new IP address settings.
o
If neither IP address is 0.0.0.0., record the displayed
address to use for remote login to the Onboard Administrator
with KVM over the management network.
6.
(Optional) Edit the Enclosure Name. The default value is the
enclosure serial number.
7.
(Optional) Edit the Rack Name. The default value is
UnnamedRack.
8.
Set the Insight Display PIN to prevent other users of the LCD from
changing the settings.
9.
Select Accept All at the bottom of the Enclosure Settings, and then
press OK to Accept all the settings to continue. If you are setting
up a single enclosure, proceed to step 11.