Product Description; 3.1 Configuration; Principle Of Operation - Vega B63-48 Operating Instructions Manual

Overvoltage protection in two-wire technology
Table of Contents

Advertisement

3 Product description

Scope of delivery
Constituent parts
Application area
Functional principle
6
3
Product description
3.1 Configuration
The scope of delivery encompasses:
Overvoltage arrester B63-48, B63-32
O-ring seal
1)
Documentation
– This operating instructions manual
– Ex specific safety instructions and, if necessary, further certifi-
cates
The following illustration shows the structure of B63-48, B63-32:
Fig. 1: Configuration of B63-48, B63-32
1
Terminals for the signal cable input (unprotected side)
2
B63-48, B63-32
3
Signal cable output to the sensor (protected side)
3.2

Principle of operation

The overvoltage arresters B63-48, B63-32 are completely enclosed in
a stainless steel housing. They can be used for VEGA sensors of the
plics
family.
®
Type B63-48 for 4 ... 20 mA and 4 ... 20 mA/HART sensors
Type B63-32 for Profibus PA and Foundation Fieldbus sensors
B63-48, B63-32 overvoltage arresters reduce any voltage surges that
may reach the signal cables to a harmless level. The devices contain
voltage-limiting components as well as gas conductors for bleeding
off impulses of up to 10 kA to ground.
Is only used with version thread M20 x 1.5
1)
B63-48, B63-32 • For 4 ... 20 mA/HART, Profibus PA and Foundation Fieldbus circuits