5 Connecting to power supply
10
11. Check all cable connections, especially the ground connection, to
make sure they are tightened sufficiently
12. Insert terminal block into its position by using the pliers. A me-
chanical coding ensures the correct position
13. Screw cable gland into the thread of B63-48, B63-32, tighten
compression nut. The seal ring must completely encircle the
cable
Fig. 2: Overvoltage protection B63-48, B63-32 after installation and connection
14. Screw the housing lid back on
The electrical connection is finished.
B63-48, B63-32 • For 4 ... 20 mA/HART, Profibus PA and Foundation Fieldbus circuits