FAN1 SUMMARY
FAN RUN:
ON
FLOW:
1465 CFM
U1 INPUT:
2.7 VDC
NOZZLE POS:
47 %
NOZZLE OUT:
2.9 VDC
VEL ALARM:
NORMAL
CFM ALARM:
NORMAL
ALARM SUMMARY
ALARM RELAY:
NORMAL
®
S
-
TATUS PAGE
MAIN
The main status page provides a brief summary of all fans. The number of fans
displayed is dependent on the configuration, 1 through 4 fans.
Time/Date are displayed in the title bar of the screen.
Fan Status is the summarized data for each fan. This includes the run input
status, fan flow and nozzle position.
Fan Type/Number/Size On the lower left corner, the fan type and number is
displayed. Fan type is displayed as C, H or M and number 1 through 4. In addition
the fan size will be displayed.
Version Number The major/minor software version number is displayed in the
bottom corner of the screen.
S
- F
1 S
TATUS PAGE
AN
UMMARY
Separate status pages are provided for each fan, 1 through 4. A fan summary
screen is presented only if the fan is defined in the configuration.
Fan Run reports the on/off status of the fun run input.
Flow represents the volumetric airflow of the fan.
U1 Input is the DC voltage measured at universal input 1, associated with Fan 1.
Nozzle Position indicates the position of the variable geometry nozzle. 0% is
reported at the minimum position, while 100% is reported at the maximum.
Nozzle Output is the DC voltage sent from the controller output to the nozzle
actuator.
Velocity Alarm indicates the status of the alarm reported if the nozzle velocity is
zero while the run input is on.
CFM Alarm indicates the status of the alarm reported if the fan flow is zero while
the run input is on.
Status Page - Fan 2 Summary, Fan 3 Summary and Fan 4 Summary same as
above if applicable.
S
- A
S
TATUS PAGE
LARM
UMMARY
Alarm Relay display the status of alarm relay (NO1). If any alarm on any fan is true,
the alarm output is controlled on and the status is reported as alarm.