Wiring For 2-Zone Temperature Control - Mitsubishi Electric Hydrobox EHSC Series Installation Manual

Table of Contents

Advertisement

5
System Set Up
Thermistor inputs
Name
Terminal block Connector
TH1
CN20
TH2
CN21
THW1
CNW12 1-2 Thermistor (Flow water temp.)
THW2
CNW12 3-4 Thermistor (Return water temp.)
THW5B
CNW5 3-4
THW6
TBI.5 7-8
THW7
TBI.5 5-6
THW8
TBI.5 3-4
THW9
TBI.5 1-2
THWB1 TBI.6 7-8
THW10 TBI.6 5-6
Ensure to wire thermistor wirings away from the power line and/or OUT1 to 16 wirings.
*1. The maximum length of the thermistor wiring is 30 m. When the wires are wired to adjacent terminals, use ring terminals and insulate the wires.
The length of the optional thermistors are 5 m. If you need to splice and extend the wirings, following points must be carried out.
1) Connect the wirings by soldering.
2) Insulate each connecting point against dust and water.
Outputs
Name
Terminal block Connector Item
OUT1
TBO.1 1-2
CNP1
OUT2
TBO.1 3-4
OUT3
TBO.1 5-6
OUT14
CNP4
TBO.2 4-6
CNV1
OUT4
CN851
TBO.2 1-2
OUT5
TBO.2 2-3
OUT6
CNBH 1-3
OUT7
CNBH 5-7
OUT8
TBO.4 7-8
OUT9
TBO.4 5-6
CNIH
OUT11 TBO.3 5-6
OUT12 TBO.3 7-8
OUT13 TBO.4 3-4
OUT15 TBO.4 1-2
OUT10 TBO.3 1-2
OUT16 TBO.3 3-4
OUTA1 TBI.4 7-8
Do not connect to the terminals that are indicated as "—" in the "Terminal block" field.
*1 For 2-zone temperature control.
*2 For 2-zone valve ON/OFF control.
N
L
N
L
N
L
TBO.2
TBO.1
1 2 3 4 5 6
OUT1 OUT2 OUT3
Wiring specification and local supply parts
Item
Name
External output function
Outputs wire
Note:
1. When the hydrobox is powered via outdoor unit, the maximum grand total current of (a)+(b) is 3.0 A.
2. Do not connect multiple water circulation pumps directly to each output (OUT1, OUT2, and OUT3). In such a case, connect them via (a) relay(s).
3. Do not connect water circulation pumps to both TBO.1 1-2 and CNP1 at the same time.
4. Connect an appropriate surge absorber to OUT10 (TBO.3 1-2) depending on the load at site.
5. Stranded wire should be processed with insulation-covered bar terminal (DIN46228-4 standard compatible type).
6. Use the same thing as the Signal input wire for OUTA1 wiring.
Item
Thermistor (Room temp.) (Option)
Thermistor (Ref. liquid temp.)
Thermistor (DHW tank water temp.) (Option) *1
Thermistor (Zone1 flow water temp.) (Option) *1
Thermistor (Zone1 return water temp.) (Option) *1
Thermistor (Zone2 flow water temp.) (Option) *1
Thermistor (Zone2 return water temp.) (Option) *1
Thermistor (Boiler flow water temp.) (Option) *1
Thermistor (Mixing tank water temp.)(Option1) *1
Water circulation pump 1 output
(Space heating/cooling & DHW)
Water circulation pump 2 output
(Space heating/cooling for Zone1)
Water circulation pump 3 output
(Space heating/cooling for Zone2) *1
2-way valve 2b output *2
Water circulation pump 4 output (DHW) OFF
3-way valve (2-way valve 1) output
3-way valve output
Mixing valve output *1
Booster heater 1 output
Booster heater 2 output
Cooling signal output
Immersion heater output
Error output
Defrost output
2-way valve 2a output *2
Comp ON signal
Boiler output
Heating/Cooling thermo ON signal
Analog output
N L L
N
1 2 3 4 5 6
TBO.3 1 2 3 4 5 6 7 8
OUT4
OUT10 OUT16OUT11 OUT12
Close Open
OUT5
Model and specifications
Use sheathed vinyl coated cord or cable.
Max. 30 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.25 mm² to 1.5 mm²
Solid wire: 0.25 mm² to 1.5 mm²
Optional part model
PAC-SE41TS-E
PAC-TH011-E
PAC-TH011-E
PAC-TH012HT-E
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
Heating
DHW
Close
Stop
Open
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Normal
Error
Normal
Defrost
OFF
ON
OFF
ON
OFF
ON
OFF
ON
N L N L
N
L
N
TBO.4
1 2 3 4
OUT15
OUT13
How to use TBO.1 to 4
Conductor
Outline view
Connect them using either way as shown above.
Signal/Max. current
Max. total current
230V AC 1.0A Max.
(Inrush current 40A Max.)
230V AC 1.0A Max.
(Inrush current 40A Max.)
230V AC 1.0A Max.
4.0A (a)
(Inrush current 40A Max.)
230V AC 1.0A Max.
(Inrush current 40A Max.)
230V AC 0.1A Max.
230V AC 0.1A Max.
230V AC 0.5A Max. (Relay)
230V AC 0.5A Max. (Relay)
3.0A (b)
230V AC 0.5A Max.
230V AC 0.5A Max. (Relay)
230V AC 0.5A Max.
230V AC 0.5A Max.
230V AC 0.1A Max.
230V AC 0.5A Max.
non-voltage contact
· 220-240V AC (30V DC)
0.5A or less
· 10mA 5V DC or more
0-10V DC 5mA max.
L
N
L
N L
TBI.4 8 7
5
6
7 8
OUTA1
OUT9
OUT8
Tool
Tool
Conductor
Top view
<Figure 5.2.2>
en
20