K8AB-VW
Setting Method
1. Setting Voltage
The voltage knob (AL1 and AL2) is used to set the voltage.
The voltage can be set to 10% to 100% of the maximum measuring voltage.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the voltage.
The maximum measuring voltage will differ depending on the model and the input terminal.
Example:K8AB-VW3 Using Input Terminal V3-COM
The maximum measuring voltage will be 600 VAC/VDC and the setting range will be 60 to 600 V.
2. Operating Time
The operating time is set using the operating time knob (T).
The operating time can be set to between 0.1 and 30 s.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the operating time.
If the input exceeds (or drops lower than) the voltage setting, the alarm indicator will start flashing for the set period and then stay lit.
Dimensions
Single-phase Voltage Relays
K8AB-VW1
K8AB-VW2
K8AB-VW3
Shunts
SDV-SH5 to SDV-SH50 (60-mV Rating)
140
120
33
Current terminal: M6 screw
Voltage terminal: M4 screw
SDV-SH300/-SH500 (60-mV Rating)
A
C
Current terminal: M10 screw (SDV-SH300),
M12 screw (SDV-SH500)
Voltage terminal: M4 screw
Model
A
B
SDV-SH300
130
30
SDV-SH500
160
40
Note: Inquire about models with a rated current of 1,500 A or larger.
8
22.5
SDV-SH75 to SDV-SH200 (60-mV Rating)
25
10.5 dia.
G
18
6
5.5
dia.
Current terminal: M8 screw
Voltage terminal: M4 screw
B
E
D
C
D
E
Resistor
110
4
36
4
120
6
41
5
A
B
C
D
Model
E
SDV-SH75
F
SDV-SH100
5.5
dia.
SDV-SH150
SDV-SH200
SDV-SH750/-SH1000 (60-mV Rating)
A
C
Current terminal: M12 screw
Voltage terminal: M5 screw
Model
A
SDV-SH750
175
SDV-SH1000
175
100
5
90
72
5
A
B
C
D
E
140 120
25
10.5
6
140 120
25
10.5
6
140 120
25
10.5
6
140 120
25
10.5
6
B
5
E
D
B
C
D
45
130
15
60
135
18
(Unit: mm)
F
G
18
36
18
36
18
43
18
43
E
30
30