Error message via PLICSCOM
VEGACAL 67 - Foundation Fieldbus
?
Instrument does not appear during connection setup
l
Incorrect termination
à
Check termination at the beginning and end points of
the bus and terminate, if necessary, acc. to the
specification
?
E013
l
no measured value available
à
Shortcircuit due to bridging of conductive buildup
between process fitting and probe
à
Remove buildup - if necessary, mount a protective tube
l
Shortcircuit in the probe, e.g. because of moisture in
the housing
à
Remove the oscillator and check the resistance
between the marked plug connections acc. to the
following illustration
Fig. 17: Check the resistance in the probe
1
Screen
2
Probe
3
Ground potential
à
There should be no contact between any of the
connections (high resistance)
à
However, if there is somehow contact, exchange
instrument or return it for repair
Maintenance and fault rectification