Setup with the indicating and adjustment module PLICSCOM
Carrying out min. adjustment
26
To be on the safe side, note the adjustment values for full and
empty. If an adjustment procedure fails, it is not necessary to
again carry out a level change.
These values can be helpful if the electronics has to be
exchanged.
Empty adjustment
Full adjustment
Tab. 2: Adjustment protocol
Tip:
For min. adjustment the vessel should be as empty as
possible, and for max. adjustment, as full as possible. If the
vessel is already full, start with max. adjustment.
Note:
If possible, the vessel should be as empty as possible for min.
adjustment.
Proceed as follows:
1 Move from the measured value display to the main menu
by pushing [OK].
Basic adjustment
Display
Diagnostics
Service
Info
2 Select the menu item "Basic adjustment" with [->] and
confirm with [OK]. Now the menu item "Min. adjustment" is
displayed.
Min. adjustment
0.00 %
=
0.0 pF
54.5 pF
3 Prepare the adjustment value for editing with [OK]. Move to
the selection window with [OK].
%
VEGACAL 67 - Foundation Fieldbus