Download Print this page

Carbolite ABF 8/28 Installation, Operating, & Maintenance Instructions page 8

After burner ashing furnace

Advertisement

Do not open the furnace door during an ashing procedure as combustion will be taking place
within the chamber.
3.2
Temperature Control
Main controller Eurotherm 3216 P1 max temp 800°C. See separate manual.
Afterburner controller Eurotherm 2132 max temp 950°C. See separate manual.
Element over-temperature controller 2132. This controller is mounted inside the furnace, and
has a set temperature of 900°C. This controller automatically switches off the elements when the
element chamber gets to hot, and then switches back on. The element over-temperature
controller is fitted as additional protecting for the heating elements. This over-temperature is self
resetting and should not need any user adjustment. It is access by removing the back panel – see
photo 3.5 below:
8
Photo 3.5
Element over
temperature
controller
MF58 – 1.06

Advertisement

loading