Gas Firing the Unit
To Start the Gas burner on new installation
1. With gas line in "off" position, install burner using gasket
and tighten down with 3 nuts to furnace.
2. Connect 110 Volt power to burner
3. Connect 24 Volt power to the burner from the DS-103 Ver-
satrol.
4. Set room thermostat 10 degrees above room temperature.
5. Allow burner to operate for 2 minutes until all air is purged
from gas line.
6. Adjust burner air to allow red flame to enter wood combus-
tion chamber about 6 inches.
7. Set the draft regulator on the chimney to .03" Water Col-
umn negative to the chimney with burner operating at least
5 minutes.
8. Gas burner air should be adjusted with CO-2 meter to in-
sure maximum burner efficiency.
9. Refer to burner manual for service tips.
Operating Instructions
32
WAYNE MODEL P250
GAS BURNER
FIG. 30